Ct Or Related Abnormality - Daikin CTXS09GVJU Service Manual

Super multi nx g-series
Hide thumbs Also See for CTXS09GVJU:
Table of Contents

Advertisement

SiUS12-814

5.20 CT or Related Abnormality

H8
Remote
Controller
Display
Outdoor Unit LED
A
5
Display
Method of
A CT or related error is detected by checking the compressor running frequency and CT-detected
Malfunction
input current.
Detection
Malfunction
The compressor running frequency is below 55 Hz (18 class) or 32 Hz (32 class).
Decision
Conditions
Supposed
Causes
Service Diagnosis
1
4
2
4
3
1
4
1
The input current is also below 1.25 A (18 class) or 0.5A (32 class).If this error repeats 4 times,
the system will shut down.
The error counter resets itself if this or any other error does not occur during the following 60-
minute compressor total running time.
Power transistor defective
Internal wiring broken or in poor contact
Reactor defective
Outdoor unit PCB defective
Troubleshooting
141

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents