Installation Condition Check - Daikin CTXS09GVJU Service Manual

Super multi nx g-series
Hide thumbs Also See for CTXS09GVJU:
Table of Contents

Advertisement

Check

6.1.5 Installation Condition Check

Check No.07
162
Installation condition check
Check the
allowable dimensions
of the air suction and
discharge area.
Normal
Does the
discharged air from
other outdoor unit cause an
increase of the suction
air temperature?
NO
Is the heat exchanger
very dirty?
NO
Is the
air flow blocked by
obstacles or winds blowing
in the opposite
direction?
NO
Abnormal
YES
YES
YES
SiUS12-814
Change the position of the air
discharge grille or the
installation location.
Change the position of the air
discharge grille or the
installation location.
Clean the heat exchanger.
Change the installation
location or direction.
Check the outside air
temperature (temperature of air
taken in by the outdoor unit).
(The outside air temperature
shall be 109˚F or lower.)
(R8379)
Service Diagnosis