6. Unpack steel wool and cut off a 1" x 3" (25 x 76mm)
strip. Save the remainder of the steel wool for future
use. Carefully stretch the strip out the full length of
the burner's ported area and then place it on the
ember tray allowing the steel wool to hang over the
burner. Next, place the rock wool loosely on top of
the steel wool and top edge of the ember retainer
along entire length of ported area of front burner.
Use individual pieces of rock wool about the size of
a quarter. Rock wool should be fluffed up and not
compressed. Rock wool must be held up by ember
retainer tray. Do not allow embers to fall on burner
and cover burner ports.
7. Ember tray ends beyond burner port area and area
in front of grate may be covered with lava rock to
suit individual appearance preferences.
8. Purge lines and test pilot operation.
9. Replace glass door. The door must be installed
before operating the fireplace. (Refer to Page 24)
10. Flame should not impinge (touch) on logs.
WARNING: Do not place rock wool, lava rock or any
other materials on the burner. Use only
certified material supplied with this fireplace.
Using uncertified materials will void the
warranty.
Ember
Tray
Steel Wool
Fig. 36 Steel wool and rock wool placement.

Speed Control Switch

1. The blower combination on/off switch and electronic
speed control is supplied loose to allow mounting in
a conveniently located wall mounted electrical box.
2. Wire speed control into black (hot) side of 120V,
60Hz line as shown in blower wiring diagram.
Temperature
Sensor
Speed
Control Switch
Black
120
Volt
White
Green
G
Fig. 37 Fan wiring diagram.
77531
Rock Wool
TL125
M
Fan
T173
Temco DV5200, DV6400 Series
CAUTION: Should this fan require ser-
vicing, the power supply must be discon-
nected.

Millivolt System

CAUTION: At installation and/or after any
service work or repairs glass door must be
removed before proceeding to lighting
instructions.
CAUTION: Label all wires prior to discon-
nection when servicing controls. Wiring
errors can cause improper and dangerous
operation.
Verify proper operation after servicing.
Burner On/Off Control
All models may be used with an optional wall switch
that turns the main burner on or off. Optional millivolt
thermostats (GFPMT) and remote control may be
substituted for the wall switch (For installation of these
options, detail instructions are provided with optional
kits).
CAUTION: If the remote receiver is located in the gas
control area (under the firebox), clearance should be
below the firebox at least 2" (51mm) to avoid high
temperatures (receiver should not be exposed to
temperatures exceeding 130°F).
Pilot Screw
E
A
OUT
IN
Manifold Pressure
Supply Pressure
Fig. 38 Pilot and valve wiring.
Wall Switch
(by others)
Thermopile
Pilot
Ignitor
To Piezo
Thermocouple
FP387
25