Gas Specifications; Gas Inlet And Manifold Pressures; High Elevations; Gas Line Installation - Temco 36CDVRRN Installation Instructions And Homeowner's Manual

Builder direct vent
Table of Contents

Advertisement

CDV Series Direct Vent Gas Fireplace
Gas Specifications
Model
Fuel
Gas Control
36CDVRRN
Nat
36CDVRRP* Prop
36CDVTRN
Nat
36CDVTRP* Prop
*Using conversion kit

Gas Inlet and Manifold Pressures

Inlet Minimum
Inlet Maximum
Manifold Pressure

High Elevations

Input ratings are shown in BTU per hour and are
certified without deration for elevations up to
4,500 feet (1,370 m) above sea level.
For elevations above 4,500 feet (1,370 m) in USA,
installations must be in accordance with the cur-
rent ANSI Z223.1/NFPA 54 and/or local codes hav-
ing jurisdiction.
In Canada, please consult provincial and/or local
authorities having jurisdiction for installations at
elevations above 4,500 feet (1,370 m).

Gas Line Installation

When purging the gas lines, the front win-
dow frame assembly must be removed.
The gas pipeline can be brought in through the rear
of the appliance as well as the bottom. Knockouts are
provided on the bottom behind the valve to allow for the
gas pipe installation and testing of any gas connection.
It is most convenient to bring the gas line in from the
rear right side of the valve as this allows fan installation
or removal without disconnecting the gas line.
The gas line connection can be made with properly
tinned 3/8" copper tubing, 3/8" rigid pipe or an ap-
proved flex connector. Since some municipalities have
additional local codes, it is always best to consult your
local authority and the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 in the USA or the CSA-B149.1 installa-
tion code.
Always check for gas leaks with a mild
soap and water solution. Do not use an
open flame for leak testing.
8
Max.
Min.
Input
Input
BTU/h
BTU/h
Millivolt
21,000
14,700
Millivolt
21,000
15,750
Millivolt
21,000
14,700
Millivolt
21,000
15,750
Natural
LP (Propane)
5.5" w.c.
11.0" w.c.
14.0" w.c.
14.0" w.c.
3.5" w.c.
10.0" w.c.
1/2" Gas Supply
FP297A
Fig. 5 Typical gas supply installation.
The gas control is equipped with a captured screw type
pressure test point, therefore it is not necessary to pro-
vide a 1/8" test point up stream of the control.
When using copper or flex connector use only approved
fittings. Always provide a union when using black iron
pipe so the gas line can be easily disconnected for
burner or fan servicing. See gas specification for pres-
sure details and ratings.
The fireplace valve must not be subjected to any test
pressures exceeding 1/2 psi. Isolate or disconnect this
and any other gas appliance control from the gas line
when pressure testing.

Remote ON/OFF Switch

Installation
1. Carefully unwrap the remote wire that is attached to
the valve. There are two 1/2" (13 mm) knockouts,
one on each side of the outer casing.
2. Remove the knockout desired and insert the plastic
snap bushing on the remote wire in the 1/2" hole.
Feed the remote wire through the outer casing.
3. Attach the wire to an ON/OFF switch and install the
switch into the receptacle box. (Fig. 6)
Remote ON/OFF Switch
or Thermostat
or Remote Control
Fig. 6 Remote switch wiring diagram.
Do not wire the remote ON/OFF wall switch
FP1224
for the gas fireplace to the 120 volt power
Remote switch
supply.
11/02
1/2" NPT x 1/2" Flare Shut-
off Valve
3/8" Flex Line
(From Valve)
FP297A
INSTA VENT FREE
UVHB26 GAS SUPPLY
7/1/98
TP
TH
Gas
Control
TP
Valve
TH
20010175
FP1224