Part X: set PIn access For servIce menUs (oPtIonal)
Creating a PIN access code allows the installer to restrict access to Service Menus. First,
a PIN access must be enabled in Service Menu 341; second, a three-digit code must be
created in Service Menu 342. After these two Service Menus are properly confi gured, the
thermostat requires the user to enter a PIN access code to enter the Service Menus.
1. On the thermostat, press the lower left and lower right areas of touchscreen
simultaneously for about fi ve seconds.
2. Press cool ▲/ ▼until Service Menu 341 (Enable/Disable PIN Access) appears in the
display. (Default value appears below Service Menu.)
Figure 15.
Service Menu
341 allows
user to restrict
access to
Service
Menus.
3. In Service Menu 341, press ▲/ ▼to change digit (fl ashing) value to "01" (see Fig. 15).
note: selecting 01 enables PIn access for the thermostat service menus, and
selecting it is necessary to show service menu 342.
4. Press cool ▲/ ▼to advance to Service Menu 342.
5. In Service Menu 342, press ▲/ ▼adjust values and create a three-digit PIN access
code. The fl ashing three-digit code appears in the clock area (see Fig. 16).
note: write down the PIn access code, and keep it in a safe place.
Figure 16.
Service Menu
342 allows
user to create
a PIN access
code.
6. Press
when fi nished.
Done
verIFY PIn access coDe
Enter the PIN access code upon entering the Service Menus. Note: Flashing digit is active;
it is changed using the ▲/ ▼keys. The active (editable) digit moves from right to left.
1. On the thermostat, press lower left and lower right area of touchscreen simultaneously
for about fi ve seconds. note Flashing three-digit code appears (see Fig. 17).
2. Press ▲/ ▼to change value of digit furthest to the right, then press Edit.
3. Press ▲/ ▼to change value of digit in middle, then press Edit.
4. Press ▲/ ▼to change value of digit furthest to left, then press Done.
Figure 17.
PIN access
code fl ashes
when user
enters Service
Menus (after
enabling PIN
access).
After step 4 is complete, the user is allowed access to Service Menus. Service Menu
100 appears.
© COPYRIGHT 2010 PECO, INC. ALL RIGHTS RESERVED.
t12000 serIes PerFormance Pro accessorIes: sensors
The following T12000 Series compatible sensors are available from PECO, providing
optimal control of the environment. In addition, following are sensor wiring diagrams for
temperature averaging, Indoor Remote Zone Sensor installation instructions, and Outdoor
Remote Sensor installation instructions.
Peco sensors
Indoor Remote
Sensor
Occupancy Sensor
Outdoor Remote
Sensor
To learn more about the benefi ts of PECO sensors visit www.pecomanufacturing.com.
Or call 1-800-874-8547 to speak with a service representative.
taBle 4. Zone sensor maXImUm lenGth anD wIre sIZe
Distance from Unit to control
000 - 150 feet
151 - 240 feet
241- 385 feet
386 - 610 feet
611 -970 feet
note:
Use appropriate wire for outdoor use.
locate & moUnt Peco occUPancY sensor (sB200-001)
Please use the installation instructions for the SB200-001 to mount the PECO Occupancy
Sensor SB200-001.
sensor wIrInG For temPeratUre averaGInG
Flashing
three-digit
code
Flashing
three-digit
code
9
model
Part
terminal
number
number
SP155-017
69308
S1
SB200-001
68375
S2
--
70327
S3
recommended wire size
22 gauge
20 gauge
18 gauge
16 gauge
14 gauge
(10K ohm) temperature sensors.
(10K ohm) temperature sensors.
P/N 70480 3220-2269 REV 00
t12000
t12500
Figure 18.
Wiring four SP155-017
Figure 19.
Wiring nine SP155-017