Peco Performance Pro T12000 Series Installation Manual

Peco Performance Pro T12000 Series Installation Manual

Thermostats
Hide thumbs Also See for Performance Pro T12000 Series:

Advertisement

Quick Links

the Peco PerFormance Pro thermostat
®
Thank you for choosing a PECO
Performance PRO™ thermostat. The Performance
PRO T12000 Series is intended for use in residential and commercial environments. It
is designed for and can support up to 3-HEAT/ 2-COOL confi gurations in conventional
systems and in heat pump applications. The Performance PRO also provides the
capability to meet the requirements for ASHRAE 90.1-2004 and California Building Code
Title 24 (2008 edition).
The Performance PRO T12000 Series is comprised of the T12000 non-programmable
thermostat models and the T12500 programmable thermostat models. The T12000
Series features a 12 square inch blue backlit display with dynamic menus, accessed
using touchscreen keys. All Performance PRO T12000 Series offer the following standard
features: auto-changeover, temporary override, optional remote sensors, occupancy
sensors, three levels of keypad lockout, a PIN access code, a furnace fi lter change
reminder. The T12500 programmable models contain: up to four scheduled events per
day, a 365-day calendar, 20 holidays, holiday override, temporary override, a Power
Harvesting feature to preserve battery life (also known as "power stealing"), Secure Digital
(SD) card capability (card not included), and optional humidity control (T12532-IAQ only).
The T12000 Series can be powered by 24 VAC or batteries or both (recommended).
The T12000 Series can control up to 7 outputs and monitor three external sensors. The
T12000 Series mounts onto any PECO Performance PRO Series wallplate.

aPPlIcatIons anD FeatUres

PECO Performance PRO is intended for use in conventional and heat pump applications.
• System mode selections: Off-Heat-Cool-Auto-Emergency
• Stages: 1 Heat/1 Cool, 2 Heat/1 Cool, 1 Heat/2 Cool; 2 Heat/ 2 Cool; 3 Heat/ /2 Cool
• Fan control: Cycling (Auto) or Continuous (On); 1 Speed
• Permanent memory: All device settings are stored in permanent memory.
• Connections for Remote Sensors (indoor, outdoor, and occupancy)
• SD card capability (card not included)
!
caUtIon!
• 24 vac low-voltage thermostat.
• Do not install on voltages higher than 30 vac.
• Use copper wire only; insulate or cap off (with wire nuts) all unused leads.
• Use care to avoid electrostatic discharge to the thermostat.
Front Panel reFerence: t12000/t12500 controls & DIsPlaY
Digital display with blue backlight
Digital display with blue backlight
Fan (On/Auto)
Temperature
(indoor)
System key
Recovery Mode
Schedule
Current time
Holiday key
Figure 1. T12000/T12500 Thermostat
Clock key
(Home Display)
Mounting holes
Wiring passage
Figure 2. T12000/T12500 Thermostat
back view (with wallplate attached).
© COPYRIGHT 2010 PECO, INC. ALL RIGHTS RESERVED.
PerFormance Pro t12000 serIes
• READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL,
OPERATE OR SERVICE THIS THERMOSTAT.
• Failure to observe safety information and comply with instructions could result in
PERSONAL INJURY, DEATH AND/OR PROPERTY DAMAGE.
• To avoid electrical shock or damage to equipment, disconnect power before
installing or servicing and use only wiring with insulation rated for full thermostat
operating voltage.
• To avoid potential fi re and/or explosion do not use in potentially fl ammable or
explosive atmospheres.
• Retain these instructions for future reference.
• This product, when installed, will be part of an engineered system whose
specifi cations and performance characteristics are not designed or controlled
by PECO. Review applications and national and local codes to assure that the
installation will be functional and safe.

ProDUct sPecIFIcatIons

Temperature Control
Range:
Differential:
Input Power:
Operating Temperature: 0° to 120°F (-17° to 48°C)
Shipping Temperature: -20° to 130°F (-28° to 54°C)
Operating Humidity:
Physical Dimensions:
Output Ratings
Voltage (50/60 Hz):
Current:

InstallatIon InstrUctIons

Select an appropriate thermostat location
Locate the thermostat about four feet (1.2m) above the fl oor on a wall in an area with good
Current day
ventilation and an average temperature, where it will be responsive to changes in room
temperature.
Cool Setpoint
(adjustable)
The Performance PRO T12000 Series may be mounted on a:
• Horizontal or vertical 2" X 4" device box
Heat Setpoint
• Horizontal 4" X 4" device box
(adjustable)
• Flat surface
Override key
Do not locate the thermostat where it can be affected by:
Keypad Lockout,
• Direct sunlight
Battery Indicator,
• Drafts or dead areas behind doors
Service Indicator,
• Radiant heat from appliances
SD card
• Concealed pipes or chimneys
• Outside walls or unheated/uncooled areas
Clean screen
Required components (not included, unless otherwise specifi ed):
• Two new AA batteries (included)
• Screws and wall anchors (included)
• Screwdrivers: Phillips (for wallplate); small fl athead (for terminal blocks)
• Drill with 3/16" drill bit (or 7/32" for plaster)
• Wirecutter and stripper
• Level
Mounting holes
• Performance PRO T12000 Series Thermostat (included)
• Performance PRO T12000 Series Thermostat Operating Manual (included)
i
note: secure Digital (sD) card feature (card not included) is a quick
confi guration tool to transfer customized settings to or from the thermostat.
For instructions, see "load sD card settings" in the operating manual.
1

InstallatIon GUIDe

warnInG
!
50° to 90° F (10° to 32° C)
1° F (0.5°C)
24 VAC (20-30 VAC) 50/60 Hz (+/- 10%) or AA alkaline batteries
(both recommended); 5mm terminals accept 14-24 AWG
stranded or solid wire.
5% to 95% RH, non-condensing
T12000/T12500 Thermostat: 5.7" W x 4.3" H x 1.3" D
with 4" x 3" / 12 square inch liquid crystal display (LCD)
20-30 VAC
0.02-1.0 A per terminal; W1 (B/O), W2 (AUX), G, A, E, Y1, Y2.
Note: Collectively, total current draw must not exceed 2.5 A.
P/N 70480 3220-2269 REV 00

Advertisement

Table of Contents
loading

Summary of Contents for Peco Performance Pro T12000 Series

  • Page 1: Installation Guide

    Series features a 12 square inch blue backlit display with dynamic menus, accessed • Retain these instructions for future reference. using touchscreen keys. All Performance PRO T12000 Series offer the following standard • This product, when installed, will be part of an engineered system whose...
  • Page 2 Be connecteD to Indoor and Outdoor Sensor and Occupancy termInal c (24 vac). Setback Input Sensor applications. Power for Heating Power for Heating Power for Cooling Power for Cooling © COPYRIGHT 2010 PECO, INC. ALL RIGHTS RESERVED. P/N 70480 3220-2269 REV 00...
  • Page 3 With the jumper removed, connect RC to the power side of the cooling transformer. Connect RH to the power side of the heating transformer; then connect both the heating and cooling commons together to terminal C (Common). © COPYRIGHT 2010 PECO, INC. ALL RIGHTS RESERVED. P/N 70480 3220-2269 REV 00...
  • Page 4 ▲/ ▼. additional system tests include (see table 2): 600, system test main output (cool); 630, system test emergency output; 640, system test economizer. © COPYRIGHT 2010 PECO, INC. ALL RIGHTS RESERVED. P/N 70480 3220-2269 REV 00...
  • Page 5 Fossil fuel backup heat Backlight Backlight temporarily on Backlight always on (low intensity, 24V only) Remote Sensor Select sensor if used. Contact PECO for information on the T12000 Series Indoor Remote Zone Sensor. No Sensor Indoor Sensor Outdoor Sensor display only...
  • Page 6 5 CPH Defines the number of cycles per hour for heating (Stage 2). Select 0 to enable ON-OFF control for (CPH) Heating Stage 2 heating. Stage 2 © COPYRIGHT 2010 PECO, INC. ALL RIGHTS RESERVED. P/N 70480 3220-2269 REV 00...
  • Page 7 Select 1 to activate the Economizer output for 10 minutes; select 0, Done or a different Service Menu to disable. Economizer Disable Economizer Output Enable Economizer Output © COPYRIGHT 2010 PECO, INC. ALL RIGHTS RESERVED. P/N 70480 3220-2269 REV 00...
  • Page 8 • Set the system setting to “Heat” and adjust the temperature setting to be temperature setting is not set above the room above the room temperature. Verify heating equipment activates. temperature © COPYRIGHT 2010 PECO, INC. ALL RIGHTS RESERVED. P/N 70480 3220-2269 REV 00...
  • Page 9 PIn access code, and keep it in a safe place. locate & moUnt Peco occUPancY sensor (sB200-001) Figure 16. Please use the installation instructions for the SB200-001 to mount the PECO Occupancy Service Menu Sensor SB200-001.
  • Page 10: Installation

    • This product, when installed, will be part of an engineered system whose specifi cations and performance characteristics are not designed or controlled by PECO. Review applications and national and local codes to assure that the installation will be functional and safe.
  • Page 11 • Make sure to select “01” in Service Menu 170. locate & moUnt Peco oUtDoor remote sensor Following are instructions on the PECO Outdoor Remote Sensor (P/N 70327). Mount the sensor where: • It can measure true outdoor ambient temperature •...
  • Page 12: Temperature Sensor

    Temperature Cooling © COPYRIGHT 2010 PECO, INC. ALL RIGHTS RESERVED. P/N 70480 3220-2269 REV 00 Performance PRO is a trademark, and PECO is a registered trademark of PECO, Inc. The PECO logo is a trademark or servicemark of PECO, Inc.