READ THESE INSTRUCTIONS CAREFULLY BEFORE
ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS
THERMOSTAT.
Failure to observe safety information and comply with instruc-
tions could result in PERSONAL INJURY, DEATH AND/OR
PROPERTY DAMAGE.
To avoid electrical shock or damage to equipment, disconnect
power before installing or servicing and use only wiring with
!
insulation rated for full thermostat operating voltage.
Before installing this control, the Voltage Selection Switch must
be placed in the correct position. See instructions.
To avoid potential fire and/or explosion do not use in potentially
flammable or explosive atmospheres.
Retain these instructions for future reference. This product,
when installed, will be part of an engineered system whose
specifications and performance characteristics are not designed
or controlled by PECO. You must review your application and
national and local codes to assure that your installation will be
functional and safe.
Use copper wire only, insulate or wire nut all unused leads.
Care should be used to avoid electrostatic discharge to the T170
!
thermostat.
This unit has configuration jumpers. You may need to reconfigure
this thermostat for your application.

applications and features

For 2 or 4 Pipe Fan Coil and On/Off Control Applications
System Selection: Off-Heat-Cool-Auto-Setback
6 Outputs: 1H, 1C, Up to 3 Fan, OA Damper
Fan Control: 1-3 Speeds
Cycling (Auto) or Continuous (On)
Automatic Fan Speed Staging
Connections for:
Fan Coil Pipe Sensor
Remote Temperature Probe
Occupancy Control
Door Switch or Setback
Condensate Overflow

specifications

Temperature Set Point Range
Differential
Memory – Back-Up
Mounting
© COPYRIGHT 2007 PECO, INC. ALL RIGHTS RESERVED.
WARNING
!
CAUTION
(TB170 models only)
AUTO
COOL
FAN ON
HEAT
AUTO LOMEDHI OF F
SYSTEM
FAN
SPEED
HOLD F/C
50 to 90°F / 10 to 32°C
EEPROM, No batteries required,
Stores settings for unlimited
time.
Installs on standard 4" x 4"
device box with a 2" x 4"
horizontal mud ring
TA/TB170 THERMOSTAT
Physical Dimensions
Agency Approvals
Electrical Ratings
Voltage
Inductive
Rating
FLA
24 VAC
NA
120 VAC
5.8
240 VAC
2.9
277 VAC
2.4
COMBINED LOAD CURRENT NOT TO EXCEED 20 AMPS
MOUNT ONLY TO A GROUNDED METALLIC BOX
LOW VOLTAGE WIRING IS CLASS 2

installation

New Installations
The thermostat should be used indoors only. It should be mounted on
an inner wall in a location with freely circulating air, and where it will be
responsive to changes in room temperature. Avoid mounting near heat
generating appliances (i.e. TV, heater, refrigerator), or in direct sunlight.
Remove Old Thermostat
1.
Turn off power to thermostat at main fuse or circuit breaker box.
Ensure that ALL power is disconnected. to prevent electri-
cal shock and /or equipment damage, disconnect electrical
power to the system at the main fuse or circuit breaker until
installation is complete.
2.
Remove the front cover of old thermostat. With wires still at-
tached, remove wall plate from the wall. If the old thermostat has
a wall mounting plate, remove the thermostat and the wall mount-
ing plate as an assembly.
3.
Before removing wires from old thermostat, label each wire
with the terminal designation from which it was attached.
Disconnect the wires from the old thermostat one at a time. do
4.
not let wires fall back into the wall.

Jumper and Circuit Board Selections

Voltage selection switch: This switch must be placed in the appropri-
ate position prior to application of power.
24V
= 24 VAC
110-277 V
= 120, 240 or 277 VAC
Jp1 Jumper selection – remote temperature sensor:
Local Sensing – Install JP1
Remote Sensing – Remove JP1 – Accessory sensors are avail-
able in standard 60" lengths but can be extended to meet applica-
tion requirements.
4.4"H x 5.8"W x 1.1"D
UL, UL Canada
(see table below)
Switching
Resistive
Pilot
LRA
Amps
Duty
NA
NA
24 VA
34.8
6.0
125 VA
17.4
5.0
125 VA
14.4
4.2
125 VA
P/N 69287 3220-2084 REV 0 PAGE 1
!

Advertisement

loading

Summary of Contents for Peco TA170

  • Page 1 Turn off power to thermostat at main fuse or circuit breaker box. or controlled by PECO. You must review your application and Ensure that ALL power is disconnected. to prevent electri- national and local codes to assure that your installation will be cal shock and /or equipment damage, disconnect electrical functional and safe.
  • Page 2 After wiring and installation is complete, energize the system. Switch Switch White/Violet White/Violet Set fan to ON. Select each fan speed (TA170 Models) to verify operation. Set the System button to AUTO, or available selection. Using the UP arrow, adjust temperature more than 5°F above the WIRING DIAGRAM room temperature to cycle on heating.
  • Page 3 • AUTO: The thermostat automatically selects the appropriate Heat If you are operating a TA170 configured with only 1 speed fan, or Cool mode depending upon the Set Point (Desired Temp) and this button is disabled.
  • Page 4 1 hour. Setback will override any user setting unless control is turned to OFF. Pipe Sensor Input: 10K PECO Remote Probe or a standard On-Off Aqua-stat can be used for summer /winter changeover. ON (closed) is Intelligent Occupancy Sensors like the SD200-001 and SD200-002 can winter heating mode and OFF (open) is summer cooling mode.