Peco Performance Pro T12000 Series Installation Manual page 6

Thermostats
Hide thumbs Also See for Performance Pro T12000 Series:
Table of Contents

Advertisement

taBle 2. aDvanceD conFIGUratIon servIce menUs (cont.)
menU
FeatUre
Range Low
290
Range High
300
Setback Low
310
Setback High
320
Zone Temp Offset
330
Keypad Lockout
340
Enable Pin Access
341
Set PIN Access
342
Code
Fan Mode
350
Enable
System Mode
360
Enable
Economizer/Outside
370
Air Damper
Minimum Deadband
380
Adjustment
Pre-Occupancy
390
Purge
Maximum Override
0=Time until next
395
Time Limit
Cycles Per Hour
400
(CPH) Cooling
Stage 1
Cycles Per Hour
410
(CPH) Cooling
Stage 2
Cycles Per Hour
420
(CPH) Heating
Stage 1
Cycles Per Hour
430
(CPH) Heating
Stage 2
© COPYRIGHT 2010 PECO, INC. ALL RIGHTS RESERVED.
oPtIons
stD.moDel
DeFaUlt
50-90 °F or
50°F (10°C)
10-32°C
50-90 °F or
90°F (32°C)
10-32°C
Off; 50-82°F or
55°F (13°C)
11-27°C
Off; 58-90°F or
90°F (32°C)
11-32°C
+/-9°F or +/-
0°F (18 °C)
4.5°C
0-3
0
0,1
0
000-999
000
1-3
3
0-3
1
0-4
0
3-10°F, 1.5-5°C
3°F
0-3 hours
0 hours
3
event; or
1-4 hours
0-6 CPH
3 CPH
0-6 CPH
3 CPH
0-12 CPH
5 CPH
0-12 CPH
5 CPH
DescrIPtIon / comments
Choose the lowest selectable temperature setpoint value.
Choose the highest selectable temperature setpoint value.
Select the heat setpoint for setback mode.
0 =
Off
50-82°F (11-27°C)
Select the cool setpoint for setback mode.
0 =
Off
58-90°F (11-32°C)
Adjusts the displayed value; may differ from actual zone temperature.
Restricts access to certain features of device; Service Menu still available if enabled.
0 =
No key pad lockout (Default)
1 =
Disables Schedule and System keys
2 =
Disables Schedule, System, and Fan keys
3 =
Disables all keys
Applies a 3 digit access code to enter Service Menu 342
0 =
Disable
1 =
Enable
Choose a 3-digit code.
1 =
ON: Fan is turned on regardless of demand.
2 =
Auto: Fan is turned on according to heating or cooling demand.
3 =
ON or Auto: Allows occupant to select either 1 or 2 above.
Allows ability to determine which system modes the occupant can select.
0 =
OFF, Auto
1 =
OFF, Heat, Cool, Auto
2 =
OFF, Heat, Cool
3 =
Heat, Cool, Auto
0 =
Off
1 =
Time Based Output
2 =
Economizer
3 =
Continuous Outside Air Damper
4 =
Cycled Outside Air Damper
Select a changeover deadband value to prevent short cycling between heating and cooling modes.
The value is adjustable to meet various HVAC system requirements.
Select to energize fan for selected number of hours (0-3) prior to all occupied events.
Restricts the duration that a temporary hold can be set. The temporary hold is limited by the maximum
amount of time as defined in this Service Menu.
0 =
Remainder of time until the next scheduled event.
1 =
1 Hour
2 =
2 Hours
3 =
3 Hours
4 =
4 Hours
Defines the number of cycles per hour for cooling (Stage 1). Select 0 to enable ON-OFF control for
Stage 1 cooling.
Defines the number of cycles per hour for cooling (Stage 2). Select 0 to enable ON-OFF control for
Stage 2 cooling.
Defines the number of cycles per hour for heating (Stage 1). Select 0 to enable ON-OFF control for
Stage 1 heating.
Defines the number of cycles per hour for heating (Stage 2). Select 0 to enable ON-OFF control for
Stage 2 heating.
6
P/N 70480 3220-2269 REV 00