the Peco PerFormance Pro t4900 school serIes thermostat
Thank you for choosing the PECO
Performance PRO
®
The T4900 provides comfort conditioning for educational environments, reducing energy
consumption and the bottom line. One-touch simplicity means users simply push the
"Teacher" key to apply an energy-effi cient School Schedule. The T4900 supports up to
3-HEAT/ 2-COOL confi gurations in conventional and heat pump applications. Users can
choose between two modes in which to operate the T4900: as a standard Performance
PRO or as a School Series.
The Performance PRO T4900 School Series is comprised of the T4932SCH-001
programmable and the T4932SCH-002 programmable thermostat with humidifi cation/
dehumidifi cation control. T4900 School Series standard features include: 4 square inches
of blue backlit display; Secure Digital (SD) card interface; locking cover; auto-changeover;
School Schedule; inputs for occupancy/ remote sensors; three levels of keypad lockout
and PIN access; furnace and UV fi lter reminders; Heat/Cool Demand Indicator; a 365-day
calendar, 20 holidays; Power Harvesting (a.k.a. "power stealing"); and humidity control
(T4932SCH-002 only).
The T4900 Series can be powered by 24 VAC or batteries or both (recommended). The
T4900 Series can control up to 7 outputs and monitor three external sensors (including a
CO
sensor). The T4900 Series mounts on any PECO Performance PRO Series common
2
wallplate.

aPPlIcatIons anD FeatUres

The PECO Performance PRO thermostat is intended for use in conventional and heat
pump applications.
• System mode selections: Off-Heat-Cool-Auto-Emergency
• Stages: 1 Heat/1 Cool, 2 Heat/1 Cool, 1 Heat/2 Cool; 2 Heat/ 2 Cool; 3 Heat/ /2 Cool
• Fan control: Cycling (Auto) or Continuous (On); 1 Speed
• Permanent memory: All device settings are stored in permanent memory.
• Connections for Remote Sensors (indoor/ outdoor/ occupancy/ CO
• SD card interface (card not included)
!
caUtIon!
• 24 vac low-voltage thermostat. Do not install on voltages higher than 30 vac.
• Use copper wire only; insulate or cap off (with wire nuts) all unused leads.
• Use care to avoid electrostatic discharge to the thermostat.
Front Panel reFerence: t4900 controls & DIsPlaY
Digital display with backlight
Current day
Temperature
(indoor)
System key
Fan key
SD Card Indicator
More key
Current time
Demand
Figure 1. T4900 Thermostat (Home Display).
Indicator
Mounting holes
Wiring passage
Figure 2. T4900 Thermostat back view (with wallplate attached).
© COPYRIGHT 2011 PECO, INC. ALL RIGHTS RESERVED.
PerFormance Pro t4900 school serIes
T4900 School Series
thermostat.
)
2
SD Card
Interface
Fan (On/Auto)
Recovery mode
Setpoint
temperature
Up and Down
keys ▲/ ▼
System mode
Teacher/
Override key
Keypad Lockout,
Battery Indicator,
Service Indicator
Mounting holes
1

InstallatIon GUIDe

warnInG
!
• READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL,
OPERATE, OR SERVICE THIS THERMOSTAT.
• Failure to observe safety information and comply with instructions could result in
PERSONAL INJURY, DEATH AND/OR PROPERTY DAMAGE.
• To avoid electrical shock or damage to equipment, disconnect power before
installing or servicing and use only wiring with insulation rated for full thermostat
operating voltage.
• To avoid potential fi re and/or explosion do not use in potentially fl ammable or
explosive atmospheres.
• Retain these instructions for future reference.
• This product, when installed, will be part of an engineered system whose
specifi cations and performance characteristics are not designed or controlled
by PECO. Review applications and national and local codes to assure that the
installation will be functional and safe.

ProDUct sPecIFIcatIons

Temperature Control
Range:
50° to 90° F (10° to 32° C)
Differential:
1° F (0.5°C)
Input Power:
24 VAC (20-30 VAC) 50/60 Hz (+/- 10%) or AA alkaline batteries
(both recommended); 5mm terminals accept 14-24 AWG
stranded or solid wire.
Operating Temperature: 0° to 120°F (-17° to 48°C)
Shipping Temperature: -20° to 130°F (-28° to 54°C)
Operating Humidity:
5% to 95% RH, non-condensing
Physical Dimensions:
T4900 Thermostat: 4.3" H x 5.7" W x 1.3"D
with 2.7" x 1.5" / 4.05 square inch liquid crystal display (LCD)
Output Ratings
Voltage (50/60 Hz):
20-30 VAC
Current:
0.02-1.0 A per terminal; W1 (B/O), W2 (AUX), G, A, E, Y1, Y2.
Note: Collectively, total current draw must not exceed 2.5 A.

InstallatIon InstrUctIons

Select an appropriate thermostat location
Locate the thermostat about fi ve feet (1.5 m) above the fl oor on a wall in an area with good
ventilation and an average temperature, where it will be responsive to changes in room
temperature.
The Performance PRO T4900 School Series may be mounted on a:
• Horizontal or vertical 2" X 4" device box
• Horizontal 4" X 4" device box
• Flat surface
Do not locate the thermostat where it can be affected by:
• Direct sunlight
• Drafts or dead areas behind doors
• Radiant heat from appliances
• Concealed pipes or chimneys
• Outside walls or unheated/uncooled areas
Required components (not included, unless otherwise specifi ed):
• Two new AA batteries (included)
• Screws and wall anchors (included)
• Screwdrivers: Phillips (for wallplate); small fl athead (for terminal blocks)
• Drill with 3/16" drill bit (or 7/32" for plaster)
• Wirecutter and stripper
• Level
• Performance PRO School Series T4900 Thermostat (included)
• Performance PRO School Series T4900 Thermostat Operating Manual (included)
i
note: secure Digital (sD) card interface (card not included) provides for quick
transfer of customized settings to or from the thermostat. For instructions, see
"load sD card settings" in the operating manual. For more information on
Peco's confi gurator, visit: www.pecomanufacturing.com/controls/
P/N 70568 3220-2287 REV 00
T4900

Advertisement

loading

Summary of Contents for Peco Performance Pro T4900 School

  • Page 1: Installation Guide

    PIN access; furnace and UV fi lter reminders; Heat/Cool Demand Indicator; a 365-day by PECO. Review applications and national and local codes to assure that the calendar, 20 holidays; Power Harvesting (a.k.a. “power stealing”); and humidity control installation will be functional and safe.
  • Page 2 Outdoor Remote mUst Be connecteD to Power for Heating Power for Heating Sensor to S1 or S3. termInal c (24 vac). Power for Cooling Power for Cooling © COPYRIGHT 2011 PECO, INC. ALL RIGHTS RESERVED. P/N 70568 3220-2287 REV 00...
  • Page 3 With the jumper removed, connect RC to the power side of the cooling transformer. Connect RH to the power side of the heating transformer; then connect both the heating and cooling commons together to terminal C (Common). © COPYRIGHT 2011 PECO, INC. ALL RIGHTS RESERVED. P/N 70568 3220-2287 REV 00...
  • Page 4 Next. additional system tests include (see table 2): 600, system test main output (cool); 630, system test emergency output; 640, system test economizer. © COPYRIGHT 2011 PECO, INC. ALL RIGHTS RESERVED. P/N 70568 3220-2287 REV 00...
  • Page 5 Fossil fuel backup heat Backlight Backlight temporarily on Backlight always on (low intensity, 24V only) Remote Sensors/ Select sensor if used. Contact PECO for information on the T4900 School Series Indoor Remote Zone Sensor Sensor. No Sensor Indoor Sensor Outdoor Sensor display only...
  • Page 6 Activates the UV Filter Timer. UV Filter timer measures the on-time for Fan output in service of heat, Timer cool, humidify, or dehumidify (Note: UV lamp life varies by manufacturer. PECO is not responsible for lamp life nor for UV filter.)
  • Page 7 5 CPH Defines the number of cycles per hour for heating (Stage 2). Select 0 to enable ON-OFF control for Stage 2 (CPH) Heating heating. Stage 2 © COPYRIGHT 2011 PECO, INC. ALL RIGHTS RESERVED. P/N 70568 3220-2287 REV 00...
  • Page 8 Select 1 (enable) to restore factory default settings for thermostat. Select 0 to disable. Disable Enable Note: Press “Done” key to complete process. Clear APCS Schedule No effect Clears APCS schedule. Menu resets to 0 after key is pressed. Done © COPYRIGHT 2011 PECO, INC. ALL RIGHTS RESERVED. P/N 70568 3220-2287 REV 00...
  • Page 9 PIn access code, and keep it in a safe place. 6. Press when fi nished. Done Figure 16. Service Menu 342 allows user to create a PIN access code. © COPYRIGHT 2011 PECO, INC. ALL RIGHTS RESERVED. P/N 70568 3220-2287 REV 00...
  • Page 10 Part XII: t4900 serIes PerFormance Pro sensors sYstem shUtDown FeatUre (oPtIonal): wIrInG DIaGrams The T4900 School Series is also compatible with PECO sensors, which provides optimal System shutdown provides the ability to shutdown all outputs via S1 Terminal control of the environment and low maintenance. Following are sensor wiring diagrams for (if enabled), and it may be used with or without application of a remote temperature probe.
  • Page 11 • This product, when installed, will be part of an engineered system whose specifi cations and performance characteristics are not designed or controlled by PECO. Review applications and national and local codes to assure that the installation will be functional and safe.
  • Page 12 Temperature Averaging. • Make sure to select “01” in Service Menu 170. locate & moUnt Peco oUtDoor remote sensor Following are instructions on the PECO Outdoor Remote Sensor. Mount the sensor where: steP 5 • It can measure true outdoor ambient temperature •...
  • Page 13: Temperature Sensor

    PUmP temPeratUre lockoUts note: heat Pump compressor lockouts (shown below) are only available if an 1. Wire the PECO Outdoor Remote Sensor to Terminal S1 and Sensor Common (SC) on outdoor temperature sensor is applied and confi gured (see table 1).
  • Page 14 • To program the number of degrees that the Heat Setpoint and Cool Setpoint may be increased and decreased, upon pushing Teacher/Override, see SM 303-SM 305. © COPYRIGHT 2011 PECO, INC. ALL RIGHTS RESERVED. P/N 70568 3220-2287 REV 00...
  • Page 15 • Occupancy Sensor is enabled —if used for application (see SM 388) • School Schedule format is applied to thermostat (see SM 100) • Pre-Occupancy Purge sets number of hours prior to occupied events (see SM 390) © COPYRIGHT 2011 PECO, INC. ALL RIGHTS RESERVED. P/N 70568 3220-2287 REV 00...
  • Page 16 © COPYRIGHT 2011 PECO, INC. ALL RIGHTS RESERVED. P/N 70568 3220-2287 REV 00 Performance PRO and School Series are trademarks and PECO is a registered trademark of PECO, Inc. The PECO logo is a trademark or servicemark of PECO, Inc.