Installation

Gas Line Requirements

The gas line must be installed in accordance with all local codes, if any; if not, follow ANSI 223.1 and
the requirements listed below.
The fireplace and gas control valve must be disconnected from the gas supply piping during any
pressure testing of that system at test pressures in excess of 1/2 psig. For pressures under 1/2 psig,
isolate the gas supply piping by closing the manual shutoff valve.
Leak test all gas line joints and the gas control valve prior to and after starting the fireplace.

Fuel

This fireplace is designed either for natural gas or for propane (but not for both). Check the sticker on
the top of the gas control valve to make sure the correct fuel is used.

Gas Line Connection

A manual shutoff valve is required within for installation (within 3' of the heater). T-Handle gas cocks
are required in Massachusetts in compliance with code 248CMR.
Installation must be performed by a qualified installer, service agency or the gas supplier (In
Massachusetts a licensed plumber/gasfitter).
The 1" diameter access hole is located 2-7/8" above the base of the fireplace. Cut
an "X" in the gasket covering the inlet and insert the gas line through the gasket.
7-3/4"
-- OR --
-- OR --

Gas Inlet Pressure:

If the pressure is not sufficient, make sure the piping used is large enough, the supply regulator is
adequately adjusted, and the total gas load for the residence does not exceed the amount supplied.
The supply regulator (the regulator that attaches directly to the residence inlet or to the propane tank)
should supply gas at the suggested input pressure listed above. Contact the local gas supplier if the
regulator is at an improper pressure.
© Travis Industries
10"
5-1/2"
The included
fitting accepts a
3/8" M.P.T. or
1/2" F.P.T.
Natural Gas
Propane
(for qualified installers only)
3/8" M.P.T to 1/2" O.D. Fitting
(Factory installed)
10" Flex Tube
(shipped with the fireplace - min. bending radius is 3/4")
Standard Input Pressure
7" W.C. (1.74 kPA)
13" W.C. (2.73 kPA)