Installation

Vent Requirements

Always maintain the
required 1" clearance (2"
clearance above the vent
when an elbow is placed
directly off the top of the
fireplace) to combustible
materials to prevent a fire
hazard. Do not fill air
spaces with insulation.
The gas appliance and vent
system must be vented
directly to the outside of
the building, and never be
attached to a chimney
serving a separate solid
fuel or gas-burning
appliance. Each direct
vent gas appliance must
use it's own separate vent
system.
In addition to the
requirements below, follow
the requirements provided
with the vent.
Altitude
Considerations
This heater has been tested at altitudes ranging from sea level to 8,000 feet (2,400 M). In this testing we have found that
-
the heater, with its standard orifice, burns correctly with just an air shutter adjustment.
Failure to adjust the air shutter properly may lead to improper combustion which can create a safety hazard.
-
Consult your dealer or installer if you suspect an improperly adjusted air shutter.
Approved Vent
Use of of the following 6-5/8" diameter co-axial gas direct vent systems:
Slide the vent sections together and turn 1/4 turn until the sections lock in place.
Screws are not required to secure the vent. However, three screws may be used to secure
vent sections together if desired.
High temperature sealant is recommended at the appliance starter section connection (use
high-temperature silicone or Mill-Pac®).
If disassembly is required, at time of re-assembly check to see if the vent creates a tight fit. If
it does not, apply high temperature sealant to the joints of the affected sections.
Horizontal sections require a 1/4" rise every 12" of travel
Horizontal sections require non-combustible support every three feet (e.g.: plumbing tape)
© Travis Industries
Use a roof flashing and storm collar
whenever passing through the roof
(Duravent Part #953 & #943 or #943S)
Use a firestop spacer whenever
passing through a ceiling
(Duravent Part #963)
8-5/8"
(220 mm)
Maintain a minimum 1" clearance from
vent to any combustible (2" above the
vent when an elbow is placed directly
off the top of the fireplace).
Manuafacturer
Simpson Dura-Vent
Selkirk Hearth Products
American Metal Products
N O T E : Always use the high-wind cap for the type of vent you are using (if applicable)
(for qualified installers only)
Vertical Termination
(Duravent Part # 991)
Minimum framing
for fire stop
8-5/8"
(220 mm)
Use a support box
on exposed vent
Use a firestop whenever
passing through a wall
Minimum
Framing for
wall thimble
Series
Model GS
Direct-Temp
Ameri-Vent
4041213
Vertical Vent
Requirements
Maintain a minimum 1"
(25 mm) clearance from
vent to any combustible
(vent is 6 5/8" (170 mm)
diameter)
Horizontal Vent
Requirements
Horizontal Termination
(Duravent Part #984)
6-5/8" Diameter
1 0 0 - 0 1 1 5 2
1 7