Gas Line Requirements; Fuel; Gas Line Connection; Gas Inlet Pressure - Travis Industries FIREPLACE XTRORDINAIR 864 HO EF GSR2 Installation Manual

With screen
Hide thumbs Also See for FIREPLACE XTRORDINAIR 864 HO EF GSR2:
Table of Contents

Advertisement

18

Gas Line Requirements

MASSACHUSETTS INSTALLATIONS - WARNING:
THIS PRODUCT MUST BE INSTALLED BY A LICENSED PLUMBER OR GAS FITTER WHEN INSTALLED WITHIN THE
COMMONWEALTH OF MASSACHUSETTS.
OTHER MASSACHUSETTS CODE REQUIREMENTS:
Flexible connector must not be longer than 36 inches.
Shutoff valve must be a "T" handle gas cock.
Only direct vent sealed combustion products are approved for bedrooms or bathrooms.
Fireplace dampers must be removed or welded in the open position prior to the installation of a fireplace insert or gas log.
A carbon monoxide (CO) detector is required in the same room as the appliance.
The gas line must be installed in accordance with all local codes and the requirements listed below.
In the absence of local codes, follow ANSI 223.1 in US/Canada or AS/NZS 5601.1 in Australia.
The fireplace and gas control valve must be disconnected from the gas supply piping during any
pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPA). For pressures under
1/2 psig (3.5 kPA), isolate the gas supply piping by closing the manual shutoff valve.
Leak test all gas line joints and the gas control valve prior to and after starting the fireplace.
This unit has been listed using the included internal gas shutoff valve.

Fuel

This fireplace is designed either for natural gas or for propane (but not for both).

Gas Line Connection

Installation must be performed by a qualified installer, service agency or the gas supplier (In Massachusetts a
licensed plumber/gasfitter).
The gas inlet accepts 1/2" MPT.

Gas Inlet Pressure

Gas Pressure
Natural Gas
Propane
If the pressure is not sufficient, make sure the piping used is large enough, the supply regulator is
adequately adjusted, and the total gas load for the residence does not exceed the amount supplied.
The supply regulator (the regulator that attaches directly to the residence inlet or to the propane tank)
should supply gas at the suggested input pressure listed above. Contact the local gas supplier if the
regulator is at an improper pressure.
© Travis Industries
Installation
Max. Input Pressure
Min. Input Pressure
7" W.C. (1.74 kPA)
5.5" W.C. (1.37 kPA)
13" W.C. (3.23 kPA)
11" W.C. (2.74 kPA)
12/27/2018 - 1423
(for qualified installers only)
Max. Manifold Pressure
3.5" W.C. (0.87 kPA)
11" W.C. (2.74 kPA)
Min. Manifold Pressure
1.6" W.C. (0.40 kPA)
2.9" W.C. (0.72 kPA)
864 HO EF GSR2 Install

Advertisement

Table of Contents
loading

Table of Contents