6-2 Operation setting/Prohibition setting from local remote controller

The setting for the control of air conditioning units (LOSSNAY, general equipments, Air To Water (PWFY)) and the permit/prohibit setting
from the local remote controller are made on this screen.
* The screen will show the status of the units at the time the screen is opened, any change that may take place after the screen is
opened will not be reflected.
* The changes made on the screen will not be reflected until the OK button is pressed.
(1) Air conditioning unit group
Item selection
frame
An orange frame
appears around
the selected item.
3Temperature
6Remote controller
operation prohibit switch
Function
1 ON/OFF
Select the operation
status (ON or OFF).
2 MODE
Select the desired
operation mode from
one of the icons below
"Mode".
3 Set Temperature Set the temperature by
using the Up/Down
arrows below "Set
Temp" function.
7Filter sign reset
Operation method
An orange frame will appear around the selected button.
An orange frame will appear around the selected mode.
* If an attempt is made to change the mode setting for the groups for which the
operation prohibition setting is enabled, the changes will not be reflected and a pale
orange frame will appear around the group.
Pressing the Up/Down arrow increases/decreases the temperature by one degree
respectively.
The settable temperature range depends on the mode and model. If the Up arrow is
pressed when the upper limit temperature is displayed. the lower limit temperature will
appear, and the Down arrow vice versa.
(Depending on the model details, the temperature range may change and Auto
setting may not be available.)
*If operation modes and preset temperature are changed from multiple controllers
(e.g., system controller and remote controller) almost simultaneously, the preset
temperature that appears on the display may be outside the settable temperature
range.
*1 This model includes DEDICATED OUTSIDE AIR SYSTEM (DOAS).
1ON/OFF switch
Model
Cooling/Dry
Standard temp
19 ~ 30°C
model
[67 ~ 87°F]
Mid temp model
14 ~ 30°C
(CITY MULTI)
[57 ~ 87°F]
Mid temp model
14 ~ 30°C
(Mr. Slim)
[57 ~ 87°F]
Low temp model
8 ~ 30°C
*1
[46 ~ 87°F]
– 27 –
2Operation mode switch
0OK
Display
Heating
17 ~ 28°C
[63 ~ 83°F]
17 ~ 28°C
[63 ~ 83°F]
14 ~ 28°C
[57 ~ 83°F]
8 ~ 28°C
[46 ~ 83°F]
8Operation status
of interlocked unit
9Fan speed of
interlocked unit
5Fan Speed
4Air Direction
aCancel
Auto
19 ~ 28°C
[67 ~ 83°F]
17 ~ 28°C
[63 ~ 83°F]
14 ~ 28°C
[57 ~ 83°F]
8 ~ 28°C
[46 ~ 83°F]