PB-1525 Wood Pellet Burner System: Installation and Operation Manual
Rev 1.0, OCTOBER 2011
Field wiring connections are made at the Terminal Strip located within the
Terminal Panel Enclosure. Figure 2.6 below details the numbered terminal
strip and connection detail. All connections are to be made to the lower,
numbered terminal connections.
Figure 2.6: Terminal Connections for the PB-1525 Wood Pellet Burner
System.
A schematic detail of the Terminal Panel Enclosure is shown below in
Figure 2.7. All wiring connections shown in this detail are factory
performed. The detail is provided for informational and troubleshooting
purposes only.
Pellergy PB‐1525 Connection Detail
Terminal #
Connection
L1 - 120V AC Input Pow er
1
2
N - 120V AC Input Pow er
3
Ground - Input Pow er
4
L1 - Auger Motor Output
5
N - Auger Motor Output
Ground - Auger Motor
6
L1 - Air Cleanout Solenoid
7
N - Air Cleanout Solenoid
8
Ground - Air Cleanout Solenoid
9
10
N.O. Contact - Alarm Output
11
N.O. Contact - Alarm Output
T1 - Tstat Dry Contact Input
12
T2 - Tstat Dry Contact Input
13
24V DC - Stack O2 Sensor (OPTION)
14
24V DC - Stack O2 Sensor (OPTION)
15
Stack Temperature Sensor (RED)
16
17
Stack Temperature Sensor (BLK)
( N O V o l t ag e)
( N O V o l t ag e)
Page 20 of 67