PB-1525 Wood Pellet Burner System: Installation and Operation Manual
Rev 1.0, OCTOBER 2011
point where a proper seal can not be made.
WARNING!
4. Fit the custom PB-1525 burner mounting plate to the boiler or
furnace. (For specific fitting details refer to documentation
included with the custom mounting plate)
5. After mounting the burner mounting plate to the boiler or furnace,
inspect to ensure that the interface between mounting plate and
boiler or furnace form an air tight seal.
6. Assemble the PB-1525 burner to the mounting plate.
7. Refractory material installed on the boiler door or mounting plate
shall be maintained as originally installed by the boiler or furnace
manufacturer to limit the surface temperature.
Pellet Hopper
Electronic Controller
(550LBS Capacity)
 The PB-1525 Wood Pellet Burner System must NOT be
operated with the boiler or Furnace door open!
 If The PB-1525 is mounted to a hinged door, an optional
interlock switch is required. This interlock is intended to
prevent the burner from operating with the door open.
Contact the boiler or furnace manufacturer for details
regarding to and availability of the interlock switch. The
Certified Installer may install an interlock switch that cuts
power to the burner system if the door is opened.
Pellet Auger
Figure 2.2a: System Overview
Auger Motor
Drop Tube
Pellet Feed Tube
Boiler or Furnace
(Not Included with System,
Show for Clarity)
Wood Pellet Burner
Page 11 of 67