terminate the unused link on ColorPower as well as the last fixture in the used link. If
you use both fixture links, you must terminate the last fixture on both links.
To terminate the ColorPower supply link, connect a male terminator to the Data Out
connector of the last fixture in the link.
Warning:
Unplug power from the ColorPower supply before making any
changes to fixture configuration on the fixture link.
Connecting ColorPower to a DMX Link
You can link one or more ColorPower units to a DMX Control desk using 5-pin DMX
data cables. Use Belden
applications) data cables with the following characteristics:
•
Two twisted pairs (4-conductors) plus a shield
•
Maximum capacitance between conductors: <15 pF/ft.
•
Maximum capacitance between conductor and shield: 55 pF/ft.
•
Maximum resistance: 20
•
Nominal impedance: 120
To link one or more ColorPower supplies as shown in Figure 2-2:
1. Connect the male XLR
connector of a 5-pin DMX
data cable to your DMX
controller's DMX Data Out
connector.
2. Connect the female XLR
connector of the 5-pin
DMX data cable to a
ColorPower supply.
3. Connect the male XLR
connector of a 4-pin XLR
DATAPLEX Color Changer
cable to the ColorPower
supply Data Out connector.
DMX Addressing
After connecting the ColorPower supply link, you will need to address the
ColorPower supply and the attached fixtures/modules for identification by the DMX
controller. A fixture on a DMX link is addressed by assigning it a Start Channel from
1-512. Start channels are set in the ColorPower menu system. You can choose
2-4
Setup and Configuration
®
9842 or equivalent (meets specifications for EIA RS-485
/1000 ft.
.
DMX Control Desk
(6 maximum per link)
ColorPower
ColorPower
Figure 2-2 Adding a ColorPower
supply link to a DMX link
Dichroic Theatre™ User Manual
ColorCommand
ColorMerge