Tekmar tekmarNet 557 Installation & Operation Manual page 46

Programmable thermostat
Hide thumbs Also See for tekmarNet 557:
Table of Contents

Advertisement

Error Messages (4 of 5)
Error Message
Description
SYSTEM CONTROL LOST ERROR
®
The thermostat can no longer communicate to the tekmarNet
system
®
control. Check for open or short circuits in the tekmarNet
communication
®
wiring. The error automatically clears once the tekmarNet
system
control has been detected.
®
If the tekmarNet
system control was intentionally removed from the
system, remove and then re-apply power to the thermostat to clear
the error.
NEED DUCT SENSOR ERROR
The dehumidifier mode has be configured to be DHUM2 or DHUM3.
These modes require a duct sensor in order to function and no duct
sensor has been detected. To clear the error message, either change
the dehumidification mode or install a duct sensor to Sensor 1.
AIR GROUP MASTER ERROR
Two thermostats have been assigned to be the master of the same
air group (cool group) number.
To clear the error, go to the Setup menu and either select a different
air group master number or set the air group master to None.
SCHEDULE MASTER ERROR
®
Two thermostats on the tekmarNet
system have been set to the
same Schedule Master number. The thermostat operates at the
temperature settings while this error is present.
To clear the error, select a different Schedule Master number, set
a different Schedule Member number, set the Schedule to Zone,
or set the Schedule to None.
SCHEDULE MEMBER ERROR
The thermostat can not longer detect its schedule master. The
temperature settings while this
thermostat operates at the
error is present.
To clear the error, select a different Schedule Member number, set
the Schedule to Zone, or set the Schedule to None.
CHANGE FILTER
The air filter requires cleaning or replacement. Once this has been
completed, go to the Monitor menu and clear the Filter Hours by
touching the number and then touch the ENTER key.
FREEZE PROTECTION WARNING
The duct temperature has dropped below 45°F (7.0°C). The second
stage cooling will be forced off at 40°F (4.5°C) and the first stage
cooling will be forced off at 35°F (1.5°C). The warning message self
clears once the duct temperature exceeds 45°F (7.0°C).
46 of 48
A Watts Water Technologies Company
© 2012
557_D - 08/12