Set Temp Menu (3 of 4)
Setting
COOL MAXIMUM ROOM LIMIT
Set the maximum room cooling limit.
Access Level: Installer
Conditions: Always available
FLOOR MINIMUM
Set the floor heating temperature while in the
event.
Access Level: Installer, User
Conditions: Sensor 1, 2 or 3 is set to Floor, and W1
Terminal is set to HRF1 or HRF2.
FLOOR MINIMUM
Set the floor heating temperature while in the
event.
Access Level: Installer, User
Conditions: Sensor 1, 2 or 3 is set to Floor, and W1
Terminal is set to HRF1 or HRF2, & Schedules are
in use or Scenes are set to All or Guest.
FLOOR MAXIMUM
Set the floor maximum temperature in order to
protect the floor covering.
Suggested settings: Tile = 90°F (32°C)
Hardwood Floor = 85°F (29°C)
Access Level: Installer
Conditions: Sensor 1, 2 or 3 is set to Floor, & W1
Terminal is set to HRF1 or HRF2.
TEMPORARY HOLD
Temperature adjustment in the home menu
can result in either permanent temperature
setting change or temporary temperature setting
change that lasts 3, 6, 9, 12 hours or until the
next scheduled event.
Access Level: Installer
Conditions: None
A Watts Water Technologies Company
Display
Range: 50 to 100°F (10.0 to
38.0°C)
Default: 100°F (38.0°C)
Range: OFF, 40 to 122°F (4.5 to
50.0°C)
Default: 72°F (22.0°C)
Range: OFF, 40 to 122°F (4.5 to
50.0°C)
Default: OFF
Range: 40 to 122°F (4.5 to
50.0°C), OFF
Default: 85°F (29.5°C)
Range: OFF or ON
Default: OFF