Table 4 Battery Cabinet Specifications - Liebert PowerSure PSI User Manual

1000 - 3000va 120v
Hide thumbs Also See for PowerSure PSI:
Table of Contents

Advertisement

Table 3
UPS specifications (continued)
Model Number
Agency
Safety
Surge
ESD
Susceptibility
Electrical Fast Transient
Emissions
Conducted Immunity
Harmonics
Flicker
Transportation
Table 4
Battery cabinet specifications
Model Number
Used w/UPS Model
Dimensions, W x D x H, in (mm)
Unit
Shipping
Weight, lbs (kg)
Unit
Shipping
Battery Parameter
Type
Quantity x Voltage x Rating
Battery Manufacturers
Backup Time
Environmental
Operating Temperature
Storage Temperature
Relative Humidity
Operating Altitude
Agency
Safety
Emissions
Transportation
PS1000RT2-120
PS1440RT2-120
FCC Part 15, Class B
PS2-48VBATT
PS1000RT2-120
PS1440RT2-120
3.43 x 22 x 17 (87 x 557 x 430)
11.8 x 27.8 x 23.5
(300 x 706 x 598)
66.1 (30)
85.1 (38.6)
Valve-regulated, nonspillable, lead acid
2 strings of 4 x 12V x 7Ah
Up to 10,000 ft. (3000m) at 95°F (35°C) without derating
27
PS2200RT2-120
UL 1778, c-UL Listed
ANSI C62.41, Category A, Level 3
(IEEE 587, Category A);
EN61000-4-5, Level 3, Criteria B
EN61000-4-2, Level 3, Criteria B
EN61000-4-3, Level 3, Criteria A
EN61000-4-4, Level 4, Criteria A
EN61000-4-6
EN61000-3-2
EN61000-3-3
ISTA Procedure 1A Certification
3.43 x 24.1 x 17 (87 x 612 x 430)
CSB, B&B Battery and EnerSys
See Table 5 - Battery run times
+32°F to + 104°F (0°C to + 40°C)
+5°F to + 104°F (-15°C to + 40°C)
0% to 95%, non-condensing
UL 1778, c-UL Listed
FCC Part 15, Class B
ISTA Procedure 1A Certification
Specifications
PS3000RT2-120
FCC Part 15, Class A
PS2-72VBATT
PS2200RT2-120
PS3000RT2-120
13.1 x 34 x 23.5
(333 x 864 x 598)
101.4 (46)
118.1 (53.6)
2 strings of 6 x 12V x 9Ah

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents