Table 4 Battery Cabinet Specifications; Table 3 - Liebert PSITM User Manual

1000 - 3000va 230v power availability
Table of Contents

Advertisement

Table 3

UPS specifications (continued)
Model Number
Agency
Safety
Surge
ESD
Susceptibility
Electrical Fast Transient
Emissions
Conducted Immunity
Harmonics
Flicker
Transportation
Table 4
Battery cabinet specifications
Model Number
Used w/UPS Model
Dimensions, W x D x H, mm (in)
Unit
Shipping
Weight, kg (lbs)
Unit
Shipping
Battery Parameter
Type
Quantity x Voltage x Rating
Battery Manufacturers
Backup Time
Environmental
Operating Temperature
Storage Temperature
Relative Humidity
Operating Altitude
Agency
Safety
Emissions
Transportation
PS1000RT2-230
PS1440RT2-230
EN 62040-1-1; TUV/GS listed; CE compliance mark
PS2-48VBATT
PS1000RT2-230
PS1440RT2-230
87 x 557 x 430 (3.43 x 22 x 17)
300 x 706 x 598
(11.8 x 27.8 x 23.5)
30 (66.1)
38.6 (85.1)
Valve-regulated, nonspillable, lead acid
2 strings of 4 x 12V x 7Ah
Up to 3,000m (10,000 ft) at 35°C (95°F) without derating
EN 62040-1-1; TUV/GS listed; CE compliance mark
27
PS2200RT2-230
PS2200RT2-230E
EN61000-4-5, Level 3, Criteria B
EN61000-4-2, Level 3, Criteria B
EN61000-4-3, Level 3, Criteria A
EN61000-4-4, Level 4, Criteria A
EN 50091-2, Class B
EN61000-4-6
EN61000-3-2
EN61000-3-3
ISTA Procedure 1A Certification
87 x 612 x 430 (3.43 x 24.1 x 17)
CSB, B&B Battery and EnerSys
See Table 5 - Battery run times
0°C to + 40°C (+32°F to + 104°F)
-15°C to + 40°C (+5°F to + 104°F)
0% to 95%, non-condensing
EN 50091-2, Class B
ISTA Procedure 1A Certification
Specifications
PS3000RT2-230
PS3000RT2-230E
PS2-72VBATT
PS2200RT2-230
PS3000RT2-230
333 x 864 x 598
(13.1 x 34 x 23.5)
46 (101.4)
53.6 (118.1)
2 strings of 6 x 12V x 9Ah

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents