Table 13 Operating Temperature Parameters; Table 14 Battery Cabinet Specifications - Liebert GXT3 User Manual

120v/208v 500va-3000va
Hide thumbs Also See for GXT3:
Table of Contents

Advertisement

Table 13
Battery cabinet specifications
Parameter
Used w/UPS Model
Dimensions, D × W × H, in (mm)
Weight, lb (kg)
Battery parameters
Qty × V× Rating
Battery Mfr./Part #
Backup Time
Environmental
Operating Temperature, °F (°C)
Storage Temperature, °F (°C)
Relative Humidity
Operating Elevation
Storage Elevation
Agency
Surge Immunity
Transportation
Table 14
Operating temperature parameters
Ambient Temperature, °C (°F)
Maximum Output
Power Factor Derating
@ Maximum Load
GXT3-48VBATT
GXT3-500RT120,GXT3-700RT120
GXT3-1000RT120,GXT3-1500RT120,
GXT3-2000RT120
19.7 x 16.9 x 3.3
Unit
(497 × 430 × 85)
24.3 x 22.4 x 10.3
Shipping
(617 x 570 x 262)
Unit
Shipping
Type
Valve-regulated, nonspillable, lead acid
2 × 4 × 12V × 9.0Ah
Panasonic/UP-RW1245; CSB/HR 1234W F2
High ambient temperatures will reduce battery life.
Up to 10,000 ft. (3000m) at 104ºF (40ºC) without derating
Safety
RFI/EMI
FCC Part 15, Class A=CISPR22 Class B
25-30 (77-86)
100%-93%
Model Number
57.3 (26)
61.7 (28)
See Table 15
32 to 104 (0 to 40)
19 to 122 (-15 to 50)
0% to 95%, non-condensing
50,000 ft. (15000m) maximum
UL 1778, c-UL Listed
IEC 62040-2 2nd Ed
ISTA Procedure 1A
30-35 (86-95)
93%-86%
37
GXT3-72VBATT
GXT3-3000RT120
GXT3-3000RT208
23.7 x 16.9 x 3.3
(602 × 430 × 85)
28.2 x 22.4 x 10.3
(717 x 570 x 262)
83.8 (38)
92.6 (42)
2 × 6 × 12V × 9.0Ah
35 - 40 (95-104)
86%-79%
Specifications

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents