Product Warranty Registration; Table 13 External Battery Cabinet Specifications - Liebert GXT2-10000RT208 User Manual

10kva, 60 hz, 120/208/240v
Hide thumbs Also See for GXT2-10000RT208:
Table of Contents

Advertisement

Table 13
External battery cabinet specifications
Model Number
Used w/ UPS Model
DIMENSIONS, Rack Mount, W x D x H
Unit (with bezel), in (mm)
Shipping, in (mm)
WEIGHT lb (kg)
Unit
Shipping
BATTERY PARAMETERS
Type
Qty x V x Rating
Battery Manufacturer / Part #
Backup Time
ENVIRONMENTAL
Operating Temp
Storage Temp
Relative Humidity
Operating Elevation
Storage Elevation
AGENCY
Safety
RFI/EMI
Transportation
14.1

Product Warranty Registration

To register for warranty protection:
• Visit the Quick Links section of our Website at:
http://www.liebert.com
• Click on Product Warranty Registration and fill in the form.
If you have any questions, please contact us at:
US: 800-222-5877
Outside the US: 614-841-6755
upstech@emersonnetworkpower.com
Contact Liebert Global Services at:
US: 800-LIEBERT (800-543-2378)
powertech@emersonnetworkpower.com
GXT2-288RTVBATT
Liebert GXT2-10000RT208
16.93 x 25.98 x 7 (430 x 660 x 178); 4U
22.64 x 33.46 x 12.40 (575 x 850 x 315)
41.6 (18.9)
50.6 (23)
Valve-regulated, non-spillable, flame retardant, lead acid
(2) x 12 x 12V x 9.0 AH
Yuasa / REW 45-12 FR
See Table 6 - Battery run times
+32°F to +104°F (0°C to +40°C)
+5°F to +122°F (-15°C to +50°C)
0% to 95%, non-condensing
Up to 10,000 ft. (3000m) at 104°F (40°C) without derating
50,000 ft. (15,000m) maximum
UL 1778, c-UL Listed (suitable for computer room applications)
FCC Part 15, Subpart B, Class A
ISTA Procedure 1A
47
Specifications
DISCONTINUED
PRODUCT

Advertisement

Table of Contents
loading

Table of Contents