1. Presentation
1.5

Extended Battery (EXB)

MX RT offers a standard backup time of 5 minutes at full load. To increase backup time, it is possible to connect
MX EXB RT modules to the UPSs for backup times up to 62 minutes (at full load).
Battery extensions for MX RT
MX
5000 RT
MX 5000 RT:
Battery Integration System Kit with Casters (86005)
Optional battery extension cable (6 ft/1.8 m)
This extended battery cable will be used instead of the standard battery cable when battery modules are distant from
each other (located in two different enclosures, for instance).
86-87050-00 A02 - Page 12
MX
EXB RT
5 min
22 min
MX
MX
EXB RT
EXB RT
41 min
The Battery Integration System is
intended for extended backup time
configurations to conveniently stack
and secure up to 5 modules on the
same cart (swivel wheels with brakes,
leveling feet, seismic side panels,
plates to lock modules, and screws
included).
62 min