Protection Features - Xantrex TC1012 Owner's Manual

True charge 2 series
Hide thumbs Also See for TC1012:
Table of Contents

Advertisement

Protection Features

Battery reverse
polarity
Over-voltage limits
Output current limit TC1012:
Over-temperature
Current derating in
ambient
temperatures
Battery over-
temperature
protection
975-0401-01-01
Protected by a replaceable DC output fuse
The Truecharge™ 2 Battery Charger will stop
charging any bank if the output voltage is above
16.6 ±0.5 Vdc.
10 ±10% A
TC1512:
15 ±10% A
TC2012:
20 ±10% A
TC3012:
30 ±10% A
TC4012:
40 ±10% A
TC5012:
50 ±10% A
TC6012:
60 ±10% A
TC1524:
15 ±10% A
TC2024:
20 ±10% A
TC3024:
30 ±10% A
TC5024:
50 ±10% A
Internal charger temperature is measured. Charger
shuts down and restarts as follows:
Shutdown at 70 °C (158 °F)
Restart at 65 °C (149 °F)
Rated current to 50 °C (122 °F)
derating to 80% Imax above 50 °C (122 °F)
Battery temperature, as sensed by the battery
temperature sensor (if installed), results in the
charger no longer charging the individual battery or
bank at a battery temperature of 70 °C (158 °F).
Protection Features
A–7