D1-09: Stop After 10Hr Bulk
•
This is a safety setting. When the bulk phase lasts more than 10 hours, this can be indi-
cation that a battery cell is damaged.
•
The absorption voltage (or the 14.4V for battery when
used) will never be reached in that case and the other cells will be over-charged result-
ing in the production of an explosive gas.
•
Therefore, the charger is disabled if the bulk phase lasts more than 10 hours.
•
This setting can be disabled because it does not always indicate a problem when the bulk
phase lasts very long. The charge current can be very low due to limited AC input current
and/or AC loads. Also, DC loads can "steal away" part of the charge current. In that case,
the bulk phase will need more time to complete and this setting must be disabled.
*
Note: When this setting is disabled, there is no safety check to protect against
over-charging.
Setting
D1-09=0
D1-09=1
(Initial setting)
D1-10: Equalize Mode Select (Storage Mode Select)
•
This setting is used for enabling/disabling the Equalize Mode.
•
In this mode, the voltage setpoint is 13.2V (for 12V battery). If Equalize mode is disabled,
then the normal float voltage will be used.
Setting
D1-10=0
D1-10=1
(Initial setting)
E Group (Auxiliary Relay):
E1 Group (Setting Aux-Relay 1 ON Condition)
E1-01: LOAD Higher than ? Amps
E1-02: LOAD Higher for ? sec
•
Use these settings to switch the Aux-Relay 1 ON. When the actual AC OUT load is above
a certain value (E1-01) for a certain time (E1-02).
•
The corresponding Aux-Relay 1 OFF condition is
E2-01: Load Lower than ? Amps and
E2-02: Load Lower for ? sec.
*
Note: If setting E1-02=0 sec (Initial setting). Then the E1-01 is ignored.
*
Note: If setting E2-02=0 sec (Initial setting). Then the E2-01 is ignored.