minimum value will result in the minimum limit. (Note: In a parallel system, this limits
per Combi-Gamma!)
Setting
C1-05=0
C1-05=1
(Initial setting)
C1-06: Load Support Level
This setting is a special setting for load support mode when the Combi-Gamma is charg-
ing and due to a sudden load, the AC IN current exceeds the AC IN Current Limit (B2-
05), the Combi-Gamma will switch to load support mode (when C1-05=1)
At that moment, the current need is unknown. The Combi-Gamma makes an assump-
tion of the magnitude of this current. This assumption is equal to AC IN Current Limit
(B2-05) multiplied by this Load Support Level (C1-06). The default factor is two.
This will prevent the circuit breaker from tripping because current provided by the IN-
VERTER minus the current drawn by the load is always lower than the rating of the cir-
cuit breaker. This happens, of course, when the AC IN Current Limit (B2-05) is correctly
adjusted on the circuit breaker.
If for instance in a
IN Current Limit (B2-05)(Normal load of generator is lower than maximum peak load) and
one knows that the load which is switched on always draws a certain current, one can con-
sider to increase this factor (C1-06) to achieve better results with sudden load changes.
D Group (AC CHARGER):
D1 Group (Charger)
D1-02: Charge Curve
Setting
D1-02=1
D1-02=2
D1-02=3
(Initial setting)
The Fixed (D1-02=1) charge curve will have a fixed
The
Adaptive (D1-02=2) and Adaptive +Battery safe (D1-02=3) curve derive the Ab-
sorption time from the Bulk time. The maximum Absorption time of these charge curves
is determined by Absorption Time (D1-06) setting.
The
Adaptive + Battery safe (D1-02=3) curve has a special regulation in the absorption
phase. The absorption phase will start when the battery voltage reaches 14.4V( for 12V
batteries) regardless of the specified Absorption Voltage (D1-03). During the absorption
phase, the voltage will increase with a fixed ramp until the voltage reaches the absorp-
tion voltage or the calculated absorption time is over in the latter case, the absorption
phase will end before the absorption voltage is reached.
Battery charger / inverter COMBI-GAMMA
Load Support Function is disabled.
Load Support Function is enabled.
generator application, the circuit breaker has a higher value than the AC
Fixed
Adaptive
Adaptive + Battery safe
Function
Function
Absorption Time (D1-06).
61
090138.02