A1-04: Init Password 1
This constant is reserved for the factory to test and set the functions.
Users are not allowed to set this constant.
Lock the constants setting (A1-01=1)
1.
Finish setting all the programmable parameters to the desired values.
2.
Change A1-01=0 (Operation only), factory setting is A1-01=1 (Constant set).
3.
Go to A1-04 and press RUN/STOP key and UP key at the same time till A1-05 parameter
occurs.
4.
Enter the desired password (max. 4 digits)
5.
Press UP key to leave A1-05
Above procedure completes locking the constants setting and no more programming se-
lection would appear. A1-01 would only display 0 (Operation only) and would not display
1 (Constants set).
Unlock the constants setting
1.
Enter the password in A1-04 to be exactly the same as the one earlier set in A1-05
2.
When the password in A1-04 matches the one earlier set in A1-05, the unlocking is com-
pleted. A1-01=1 (Constants set) would appear again for programming.
B Group (General):
B1 Group (Output Frequency)
B1-01: Output frequency
B1-01 is used to set the output frequency at INVERTER AC output
Setting
B1-01=0
(Initial setting)
B1-01=1
B2-08: AC IN Frequency Range
Setting
B2-08=0
B2-08=1
(Initial setting)
54
090138.02
50Hz at INVERTER AC output
60Hz at INVERTER AC output
When B1-01=0: Acceptable AC input frequency is 50Hz ±5Hz (45~55Hz)
When B1-01=1: Acceptable AC input frequency is 60Hz ±5Hz (55~65Hz)
Accept wide AC input frequency range between 45~65Hz
Function
Function
Battery charger / inverter COMBI-GAMMA