B Group: General - Vetus Combi-Gamma COMBI1512 Operation And Installation Instructions Manual

Inverter - battery charger
Table of Contents

Advertisement

B2 Group (Auto Transfer Switch)
B2-01: AC IN Low Disconnect
Use constant B2-01 to determine the AC IN voltage below which level the ATS (Auto
Transfer Switch) will switch off.
This voltage level will always lie below the
changing this level will also change the AC IN Low Connect (B2-02) level.
B2-02: AC IN Low Connect
This setting forms a pair with
mines the AC IN low voltage at which level the ATS will switch on. This should lie above
AC IN Low Disconnect (B2-01) level to prevent continuous switching off the ATS when
the voltage is fluctuating around the level.
In fact, the parameter which is changed is the difference between
(B2-01) and AC IN Low Connect (B2-02).
The result of this is that when changing B2-01 level, this level (B2-02) also changes.
*
Note: B2-02 can be ignored for a short time when AC IN Waveform Check (B2-06) is
disabled (B2-06=0)
When the AC IN voltage drops due to the increasing charge current, the AC CHARGER
will take care that the voltage does not drop below this level.
B2-02=B2-01+offset voltage
B2-03: AC IN High Connect
This setting forms a pair with
determines the AC IN high voltage at which level the ATS will switch on. This should lie
below the AC IN High Disconnect (B2-04) level to prevent continuous switching of the
ATS when the voltage is fluctuating around that level.
In fact, the parameter which is changed is the difference between
nect (B2-04) and AC IN High Connect (B2-03).
The result of this is that when changing B2-04 level, this level (B2-03) also changes.
B2-03=B2-04–offset voltage
B2-04: AC IN High Disconnect
Use constant B2-04 to determine the AC IN voltage above which level the ATS will switch
off.
This voltage level will always lie above the
changing this level will also change the AC IN High Connect (B2-03) level.
B2-05: AC IN Current Limit
Use constant B2-05 to set the specific maximum AC input current. This value is very
important for both battery charger and inverter output load support.
When using constant B2-05, the values determine the actual AC current limit.
Battery charger / inverter COMBI-GAMMA
AC IN Low Connect (B2-02) level. In fact,
AC IN Low Disconnect (B2-01). With this setting, one deter-
AC IN High Disconnect (B2-04). With this setting, one
AC IN High Connect (B2-03) level. In fact,
AC IN Low Disconnect
AC IN High Discon-
090138.02
55