Specifications - GE Digital Energy LP 11 Operating Manual

Uninterruptible power supply 3-5-6-8-10 kva
Table of Contents

Advertisement

UPS Type
Output power (kVA/kW)
AC input voltage
Input frequency
AC output voltage
Output frequency
System efficiency (full load)
Line input breaker (MCB, D-type)
Bypass input breaker (MCB, D-type)
Input/output connectors
INPUT
AC input voltage range
at 100% load
at 50% load
at 25% load
Input frequency range
Input current wave form
Input power factor
Max. input current (A)
Inrush current
DC output voltage
BATTERY CHARGER
Characteristic
DC input voltage range
DC output voltage at 20 °C
LP 3-11
LP 5/6/8/10-11
Output current limit (Adc)
OUTPUT CONVERTER
Output power at pf. = 0.8, VA*
Semiconductor
AC output voltage nominal
Output voltage tolerance
Typical overload
(temp. dependent)
Output frequency
Freq. tracking range
Output wave form
Max. phase difference input-output
Harmonic distortion
Power factor range
Output derating altitude
Protection
The output is protected against connection to the mains
* according to EN 50091-1
OPM_LPE_11X_3K0_10K_1GB_V041

10 - Specifications

:
LP 3-11
LP 5-11
:
3/2.4
5/4
:
220-240Vac
:
50/60 Hz
:
230V
:
50 or 60 Hz, std. 50 Hz; selectable on front
:
88%
:
32A
32A
:
32A
32A
:
terminals at rear of unit
:
172 - 285 V
:
147 - 285 V
:
132 - 285 V
:
40-70 Hz
:
sinusoidal
≥ 0.99
:
:
16
28
:
none
:
380 V
:
U/I-characteristic, constant current charging until float voltage, then constant
voltage charging and boost charge mode for fast recharging of batteries
:
350-450 V
:
float: 162.5 V boost: 177 V
:
float: 274 V boost: 295 V
:
2.0
2.0
:
3000
5000
:
IGBT
:
220/230/240V (user selectable)
:
± 1% static resistive load
± 2% measured crest load 2.5:1
± 2% dynamic mean deviation over one half cycle for 100% of rated load
applied or removed
110% ≥ 20 minutes
:
130% ≥ 3.5 minutes
150% ≥ 2 minutes
:
60 or 50 Hz selectable, ± 0.1%, unless synchronized with the mains
:
± 2/4/6% of nominal, user selectable
:
sine wave
:
max 7°
:
2% max. with linear load
:
Any lagging or leading power factor is permitted within the specified rating to
pf. 0.5
:
Till 1000m no derating
Above 1000m 12.5% per 1000m, max. 4000m
:
Automatic shut down (or transfer to bypass, if bypass is available) in case of
- low/high DC voltage
- overtemperature
- overload / short circuit
33
LP 6-11
LP 8-11
6/4.8
8/6.4
32A
40A
32A
40A
28
40
2.0
3.6
6000
8000
GE DE LP 11 UPS: User manual 4.1 (GB)
LP 10-11
10/8
50A
50A
50
3.6
10000

Hide quick links: