GE Digital Energy LP 11 Operating Manual page 35

Uninterruptible power supply 3-5-6-8-10 kva
Table of Contents

Advertisement

UPS Type
AUTOMATIC BYPASS SWITCH
The automatic switch provides transfer of the load to the mains voltage without any interruption of the supply. The transfer is
initiated by a signal from the output converter protection circuit in case of an overload or high temperature.
When the conditions return to normal the load is automatically transferred back to the output converter. The automatic
bypass switch can be disabled by the end-user.
Bypass voltage limits
Transfer transients
Frequency tracking range
Slew rate
BATTERY
Battery type
Nominal voltage (V) / capacity (Ah)
Number of batteries
Capacity of standard battery set
Battery recharge time
Battery service life
Battery discharging
Runtime in minutes
VA / Watts
1000 / 800
2000 / 1600
3000 / 2400
5000 / 4000
6000 / 4800
8000 / 6400
10000 / 8000
BATTERY EXTENSION PACKS
Sheet steel cubicle
Dimensions (hxwxd, mm)
Battery
Weight with battery
Battery pack A (voltage V / capacity Ah)
Total capacity (Ah)
Typical runtime, 100% / 50% load, min.
Number of packs required
Extension B (voltage V / capacity Ah)
Total capacity (Ah)
Typical runtime, 100% / 50% load, min.
Number of packs required
For more info see section 7.1
ENCLOSURE
Sheet steel cubicle
Colour front
Colour cabinet
Protection
Dimensions (hxwxd, mm)
(height with castors)
Weight (with batteries)
GENERAL DESIGN CRITERIA
Mechanical
Humidity
Safety
EMC
Surge capability
OPM_LPE_11X_3K0_10K_1GB_V041
:
LP 3-11
LP 5-11
:
±10% of nominal
:
typically 2% mean deviation over one half cycle.
:
± 2/4/6% of nominal (user selectable)
:
max. 1Hz/sec or 5Hz/sec (user selectable)
:
Sealed and maintenance free
:
12/7
12/7
:
12
20
:
7 Ah
7Ah
:
1.5 - 3 hours for 80% capacity
:
up to 6 years (depending on operating conditions)
:
self discharge current 0.35 mA
discharge end voltage of the battery depending on the actual load
10.5Vdc < 0.2 CA till 9.0 Vdc > 2 CA
When the LP-11 is in sleeping mode the inverter will be switched off, battery
charger and rectifier are in operation
:
30
60
:
15
40
:
10
18
:
-
10
:
-
-
:
-
-
:
-
-
:
VSDA1
:
537x313x590
:
240Vdc/7Ah or 240Vdc/14Ah
:
70kg or 120kg (without batt: 20kg)
:
n.a.
240/7
:
n.a.
14
:
n.a.
25/60
:
n.a.
1
:
n.a.
240/14
:
n.a.
21
:
n.a.
45/90
:
n.a.
1
:
VSD1
VSD1
:
aluminum
:
RAL 9010 (white)
:
IP 20
:
537x313x590
537x313x590
:
85kg
110kg
:
IP20
:
95% non condensing
:
EN 50091-1; EN 60950; IEC 950
:
EN 50091-2
:
IEC 1000-4-5 (6kV 1.2/50µs, 3kA 8/20µs)
34
LP 6-11
LP 8-11
12/7
12/12
20
20
7Ah
12Ah
60
120
40
60
18
40
10
22
8
17
-
11
-
-
240/7
240/7
14
19
21/50
22/50
1
1
240/14
240/14
21
26
35/75
33/70
1
1
VSD1
VSD2
537x313x590
680x313x720
115kg
165kg
GE DE LP 11 UPS: User manual 4.1 (GB)
LP 10-11
12/12
20
12Ah
120
60
40
22
17
11
8
240/7
19
16/39
1
240/14
26
25/57
1
VSD2
680x313x720
170kg