Uninterruptible power supply 3-5-6-8-10 kva
Table of Contents

Advertisement

Model
Heat dissipation
100% load
50% load
LP
W
Btu/hr
W
Btu/hr
8-11
520
872
2976
1774
10-11
988
3371
545
1860
h
w
LP 8/10-11 installation drawing
Dimensions
Weight
Air flow
h
w
d
100%
load
mm
mm
mm
kg
m3/hr
313
720
165
660
680
313
720
170
660
680
d
CASTORS
Amb.
Rel.
Altitude
Branch
temp.
humidity
(max 4000m)
protec-
non-cond.
tion
slow
°C
%
m
-10-40
<95
50
<1000, derating
-10-40
<95
50
12.5% per 1000
CABLE CLAMPS
Input/output
Minimum free space
wiring
required
front
side
rear
A
mm2
AWG
mm
mm
mm
10
8
100
50
200
10
8
100
50
200
MANUAL BYPASS SWITCH
BATTERY PACK CONNECTOR
CONTROLS / FUSES
OPTION SLOTS
I/O TERMINALS
INPUT
OUTPUT
RS232 / CONTACT INTERFACE
EARTH CONNECTION
IS ESSENTIAL
SUB-D PINNING
5 - COMMON
9 - GENERAL ALARM
4 - NOT USED
8 - MAINS FAILURE
3 - SERIAL DATA IN / UPS SHUTDOWN
7 - PLUG&PLAY / RTS
2 - SERIAL DATA OUT
6 - BYPASS ACTIVE
1 - BATTERY LOW
Bottom
x
y
mm
mm
184
578
184
578
NORMAL: POSITION 1
(LOAD ON UPS)
SERVICE: POSITION 2
(LOAD ON BYPASS)
STATIC
UPS
MAINS
BYPASS
ON
OFF
RS232 / CONTACT, SEE BELOW
SNMP CARD OR RELAY CARD
RPA CARD
PARALLEL OPERATION
1-2 BATTERY
DISCONNECTED
3-4 EMERGENCY
SHUTDOWN