Ratings
Voltage Amperes (VA) with computer type load
Watts (W) with resistive load
Input thermal circuit breaker (A)
Internal input fuse 250V, slow (A)
Input converter
AC input voltage
Input current waveform
Input current (A) at nominal input voltage
Input power factor
Input frequency range
Inrush current
Output converter
AC output voltage
AC output voltage tolerance
Output frequency
Output frequency range
Output waveform
Harmonic distortion
Power factor
Crest factor (peak to RMS current)
Capacity appliance outlets
Bypass
AC input voltage range
Frequency tracking rate
Frequency tracking range
Phase difference
Typical transfer time, msec
Overload capability
Overload behaviour during battery operation
Overload behavior during bypass operation
Batteries (ratings given for 77ºF)
Nominal voltage (Vdc)
Number / Ah batteries
Type
Service life
Recharge current
Battery recharge time
(batt. discharged at 100% load)
Runtime in minutes at typical load (75%)
VA/Watts
250/225
500/450
700/630
1000/900
1500/1350
1920/1740
General
Weight UPS (lbs/kg)
Dimensions UPS (HxWxD) - inch
Dimensions UPS (HxWxD) - mm
Enclosure / protection
Battery pack
Nominal voltage (Vdc)
Max. Number / Ah battery extension pack
Weight (lbs/kg)
Dimensions (HxWxD)
Environment
Safety
Electromagnetic compatibility
Ambient temperature
Audible noise at 1 meter
Max. relative humidity
Modifications reserved
GE_UPS_OPM_VHU_0K7_3K0_XUS_V011.docx
Critical Power
:
700
1000
:
700
1000
:
630
900
:
8
12
:
15
15
:
60 - 140 V
:
sinusoidal, EN 61000-3-2 (IEC 555-2) compliant
:
6.6
9.1
:
1
:
45 - 66 Hz
:
none
:
100 / 110 / 115 / 120 / 127 V (selectable)
:
± 2%
:
auto selectable or 50 / 60 Hz, front selectable
:
nominal ± 0.05% unless synchronized to the mains
:
sine wave
:
< 1% with linear load
:
0.9
:
suitable for loads with c.f. up to 3:1
:
max. 20A per outlet (+ 1 high power outlet max. 20A, on 2000VA model only)
(+ 1 high power outlet max. 30A, on 3000VA model only)
:
selected output voltage -15% to +10%
:
2 Hz/sec.
:
nominal ± 10% / ± 2% selectable
:
< 1º typical (max. 7º during tracking frequency range)
:
1
:
fully protected against overload and short circuits
:
110% 4 minutes
:
150% 2 seconds
:
depends on rating of thermal circuit breaker
typical:
125% of TCB value for 200 seconds
200% of TCB value for 10 seconds
300% of TCB value for 4 seconds
:
36
36
:
3/7
3/9
:
sealed lead acid, maintenance free
:
up to 6 years (depending on use)
:
1.5 A
:
3 hours for 90% capacity, std battery
:
12
12
:
22
35
:
12
18
:
8
12
:
8
:
:
:
35/16
37/17
:
3.4x17.2x18.5
:
87x438x470
:
steel-plastic / IP20
:
36
36
:
3/14
3/14
:
60/27
:
3.4x17.2x18.5inch
:
87x438x470 mm
:
UL 1778, 5
Edition
th
:
EN 62040-2
:
32 to 104ºF (0 to +40ºC)
:
< 45 dB(A), load and temperature dependent
:
95% (non-condensing)
Operating Manual VH700 UL, VH1000 UL, VH1500 UL, VH2000 UL & VH3000 UL
1500
2000
1500
1920
1350
1740
18
20
30
30
13.9
16
72
72
6/7
6/9
11
12
58
70
28
36
21
27
13
20
7
12
8
64/29
71/32
3.4x17.2x21.3
87x438x540
72
72
3/14
3/14
101/46
3.4x17.2x21.3 inch
87x438x540 mm
3000
3000
2700
30
30
24
72
6/9
7
102
48
33
22
12
8
8
77/35
3.4x17.2x23.0
87x438x585
72
3/14