Specifications - GE GT Series User Manual

Digital energy uninterruptible power supply 5/6/8/10 kva
Table of Contents

Advertisement

9 SPECIFICATIONS

Model
Ratings
Power ratings depending on input voltage
100V / 200V
110V / 220V
115V / 230V
120V / 208V
120V / 240V
127V / 220V
:
Input thermal circuit breaker (A)
Internal input fuse 250V, slow (A)
Input converter
AC input voltage
AC input voltage range
Input current waveform
Input current (A) at nominal input voltage
Input power factor
Input frequency range
Input phase (L1 to L2)
Inrush current
Output converter
AC output voltage
AC output voltage tolerance
Output frequency
Output frequency range
Output waveform
Harmonic distortion
Power factor at nominal input voltage
Crest factor (peak to RMS current)
Capacity appliance outlets
Bypass
AC input voltage range
Frequency tracking rate
Frequency tracking range
Typical transfer time, msec
Overload capability
Overload behavior during battery operation
Overload behavior during bypass operation
Batteries (ratings given for 25ºC)
Nominal voltage (Vdc)
Number / Ah batteries
(in battery kit and battery ext. pack)
Type
Service life
Recharge current
Battery recharge time
(batt. discharged at 100% load)
Runtime in minutes
at typical load (75%)
25%
50%
75%
100%
General
Weight UPS kg
Dimensions UPS (h
w
d)
x
x
Weight battery pack kg
Dimensions battery pack
Enclosure / protection
Environment
Safety
Electromagnetic compatibility
Ambient temperature
Audible noise at 1 meter
Max. relative humidity
Color
modifications reserved
:
GT5000
GT6000
:
VA / W
VA / W
:
4000 / 3400
4800 / 3400
:
4500 / 3800
5400 / 3800
:
5000 / 4000
6000 / 4200
:
4800 / 4200
5200 / 4200
:
5000 / 4200
6000 / 4200
4800 / 4200
5200 / 4200
:
30
30
:
30
30
:
Nominal: 120 / 208 V
:
100/(173-200), 110/(190-220), 115/(198-230), 120/(208-240), 127/(220) V
:
:
20
20
:
:
:
120° / 180° / 240° ±10°
:
40
40
:
100 / 110 / 115 / 120 / 127 V (selectable)
:
L-N ± 3%; L1-L2 ± 5%
:
50 / 60 Hz, auto selection
:
nominal ± 5% with mains synchronizing
:
:
< 3% with linear load, < 5% with non-linear full load
:
0.87
0.8
:
:
with 55A Terminal Block
:
± 15% of selected output voltage
:
:
± 5% of selected frequency
:
:
fully protected against overload and short circuits
:
130% during 10 seconds
:
200% during 2 seconds
: depends on rating of thermal circuit breaker
125% of TCB value for 200 seconds
200% of TCB value for 10 seconds
300% of TCB value for 4 seconds
:
144
144
:
12pcs / 8Ah
12pcs / 8Ah
:
:
up to 5 years (depending on use)
:
:
6 hours for 90% capacity
:
8
:
31
31
:
14
14
:
8
:
5
:
30.3 Kg (67 lbs)
:
176x430x592 mm (6.9x16.9x22.55 in)
:
43 Kg (94.7 lbs)
:
87x430x592 mm (3.47x16.9x2255 in)
:
:
:
EMI: FCC CFR47 Part 15, class A, ESD: IEC61000-4-2, level 4
RS: IEC61000-4-3, level 3, EFT: IEC61000-4-4, level 4, Surge: IEC61000-4-5, level 3
ANSI C62.41 (IEEE587) Category A (level 3) & B (level 1)
:
:
< 55 dB(A), load and temperature dependent
:
90% (non-condensing)
:
41
GT8000
VA / W
6400 / 6400
7200 / 7200
8000 / 8000
8000 / 6900
8000 / 8000
8000 / 6900
60
30*2
sine wave
40
> 0.97
40 - 70 Hz
40
L-N ± 2%; L1-L2 ± 5%
sine wave
0.86
≤ 3 : 1
1Hz/s
0
130% during 1 minute
200% during 5 seconds
overload protection
110% for 300 seconds
130% for 30 seconds
200% for 5 seconds
288
24pcs / 8Ah
REW45-12 FR
1 A
3 hours for 90% capacity
8
9
40
16
8
9
5
5
49.3 Kg (109 lbs)
267x430x660 mm (10.5x16.9x26 in)
91 Kg (200.4 lbs)
173x430x660 mm (6.8x16.9x26 in)
steel-plastic / IP20
UL1778
0 to +40ºC
Black - RAL 9005
User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
GT10000
VA / W
8000 / 6400
9000 / 7200
10000 / 8000
8700 / 8000
10000 / 8000
8700 / 8000
60
30*2
40
40
0.92
288
24pcs / 8Ah
9
40
16
9
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents