GE Digital Energy LP 11 Operating Manual page 22

Uninterruptible power supply 3-5-6-8-10 kva
Table of Contents

Advertisement

CAPACITOR C1
CAPACITY LOW
LOADnotPROTECTED
INVERTER OFF
LOADnotPROTECTED
BATTERY DEPLETED
LOADnotPROTECTED
BATTERY LOW
UPS SHUTDOWN
LEFT 2 MINUTES
BYPASS ERROR
FUSE FAILURE
INPUT ERROR
FUSE FAILURE
INTERNAL BATTERY
FUSE FAILURE
EXTERNAL BATTERY
FUSE FAILURE
REPLACE BATTERY
INPUT out LIMITS
137V
50.0Hz
BYPASSoutLIMITS
197V
50.0Hz
INPUT AND OUTPUT
NOT SYNCHRONIZED
AUTONOMY TIME
LEFT
0:09:41
OPM_LPE_11X_3K0_10K_1GB_V041
The main DC-capacitor needs replacement due to aging or failure
Due to a failure the output converter's output is not available. As a result the
load may have been transferred to bypass.
The remaining runtime is zero. As a result the load may have been transferred
to bypass.
The remaining runtime is less than the set time (standard 2 minutes). This text
alternates with the following screen:
The output voltage can be lost after the indicated time due to discharged
battery. Controlled shutdown of any computer equipment is absolutely
necessary at this point. (Using the RS232 or SNMP communications interface,
this procedure can be initiated automatically on unattended systems). If the
UPS operates at 100% load, the shutdown procedure should be completed
within 2 minutes after the 'battery low' alarm started. When the batteries are
fully discharged, the UPS is no longer able to power the connected equipment.
The static bypass MCB (rear panel, 9) is in 'off' (down position): no bypass
voltage available. Mains voltage is available. If not manually operated, this may
have been caused by an overload situation.
The mains MCB (rear panel, 8) is in the 'off' (down position): no line voltage
available, bypass voltage is available. If not manually operated, this may have
been caused by an internal system failure.
The internal battery fuse is defective; this may have been caused by an
internal system failure. This alarm also appears if no batteries are installed.
The (custom-built) battery extension set has been disconnected from the
system: its energy reserve is not available. See 4.5.2 or 4.5.4 step 9 for details.
The batteries are (almost) chemically worn out. If the batteries are aged, they
must be replaced as soon as possible to ensure full protection for your
equipment (see section 8.3).
The mains voltage or mains frequency are outside UPS input tolerance (see
chapter 10, specifications)
The mains voltage or mains frequency are outside bypass input tolerance but
inside UPS (rectifier) input tolerance (see chapter 10, specifications). Bypass
operation is inhibited: if for whatever reason the output converter is unable to
deliver the required output, output power is lost.
The output converter frequency is not synchronized to the mains (input)
frequency. In this situation the automatic bypass switch is not able to transfer
the load from output converter to bypass and reverse: automatic bypass
operation is inhibited: if for whatever reason the output converter is unable to
deliver the required output, output power is lost. (see section 3.4).
Synchronization is only possible if the mains frequency remains within
certain limits (see chapter 10).
The remaining runtime. This figure is counted down during battery operation
until either the mains returns or the batteries are depleted.
21
GE DE LP 11 UPS: User manual 4.1 (GB)