Appendix B: Specifications

Rack Model #
Tower Model #
Topology
Output VA/Watts
Output Power Factor
Output voltage (Battery Mode)
Output Voltage (Utility Mode)
Output Frequency
AVR Boost/Trim
Output voltage THD
Input voltage at full load
Input current at nominal voltage
Input – Buck / Comeback
Input – Boost / Comeback
Low line loss / comeback
High line loss / comeback
Input Frequency (Hz)
UPS efficiency
Voltage Drop in Transformer in
Utility mode @ 100% load
Acoustic noise (dBA)
Ambient temperature ⁰F (⁰C)
Humidity
# of Outlets (NEMA 5-15R)
Input line 6Ft, Cord
Enclosure Specifications for Rack
Mount Models
Fan speed
Front display
Audio Alarm: Battery mode:
Battery low/charger fault:
UPS fault:
Overload:
Sleep mode
Alarm silence:
UPS parameters user configurable
Battery replacement procedure
Battery type
Battery capacity
Back-up time @ full load
Recharge time to 90% cap
Charging Current
Min. Battery Start up Voltage
Transfer time.
Input protection
Surge capability, peak current
capability
Communication
Overload Protection
Short circuit protection
SNMP Card Slot
Note:
Characteristics are subject to change without prior notice.
Modifications Reserved
OPM_ITS_USM_M06_M20_0US_V011 (09/2007)
UPS0600ITSIR
UPS0600ITSIT
600VA/360W
120V, Pure sine wave at +/-5% of nominal, -10% of nominal after low battery warning
50/60 Hz +/- 0.5% (Auto sensing: default 60Hz or follows latest I/P frequency)
<5%, @ 100% resistive load with 80% battery capacity
6 max.
On Battery: >80% with 100% resister load. On Utility: >95% @ full charged battery & 100% Resistive load
<40dBA (1 meter from surface)
Tower: 4, Rack Mount: 4
Tower: Temperature and Load dependent, Rack Mount: Constant
34W, Maintenance free sealed Lead Acid battery with 2 to 4 years typical lifetime
(12V /34W) x 2
10 mins
16
UPS automatic shutdown if overload exceeds 110% nominal at 20 sec and 125% at 5 sec
UPS1000ITSIR
UPS1000ITSIT
Line Interactive
1000VA/600W
0.6
120V, +/-10%
Boost 17%, Buck 14%
120V, +/-10%
10 max.
128/131, +/- 3V
109/112, +/- 3V
90/95, +/- 3V
150/145, +/- 3V
50 or 60 Hz +/-5Hz (Auto sensing)
< 2V
3,500 meters max. elevation, 32-95 ⁰F (0-35 ⁰C)
0-95% humidity non-condensing,
Tower: 4, Rack Mount: 4
Tower: 6, Rack Mount: 4
NEMA 5-15P
Compatible with 19" Rack
LED
Slow beeping sound (about 0.25Hz)
Rapid beeping sound (about 1Hz)
Continue beeping sound
Continue beeping sound
Dual rapid beeping sound every 5 sec.
by push-on button for 1 second
Software Via RS-232
Hot swappable
(12V/34W) x 2
4-5 mins
4 hours
1.5A
16
Typical 4~6 ms.
Breaker
6500A/780 Joule
USB and RS232 (One port works at a time)
Yes
SNMP slot provision. Must be integrated in the UPS
UPS1500ITSIR
UPS2000ITSIR
UPS1500ITSIT
UPS2000ITSIT
1500VA/900W
2000VA/1200W
15 max.
<45dBA (1 meter from surface)
Tower: 6, Rack Mount: 6
(12V/34W) x 3
4-5 mins
24
20 max.
NEMA 5-20P
(12V/34W) x 4
4-5 mins
32
26