5.3 Use

Once the unit is in operation, there is no need to switch the unit on/off during use.
If the manual bypass switch (rear panel, 10) is in position '1', switching off by the on/off switch (rear panel, 7)
results in a total absence of the output voltage (also the bypass voltage) of at least 5 seconds.
If an emergency shutdown switch has been installed (see 4.5.1 or 4.5.3, step 7) the UPS will stop immediately
when the switch is opened. Restart is only possible after closing the switch and turning the UPS off and on
again with the UPS on/off switch (rear panel, 7).
The UPS is operated via the push-buttons (front panel, 2-3-4) and the LCD display (front panel, 1). Furthermore
the UPS can be controlled via the RS232/contact interface port (rear panel, 12a). For more information see 6.1.
The menus on the display can be divided into 5 groups:
1
standard screen
2

information menu (5.3.1)

3
status- and alarm menu (5.3.2)
4
service menu (5.3.3)
5
set-up menu (5.3.4)
The standard menu shows UPS model and actual load.
5.3.1 Information menu
When the default screen is displayed the first information screen can be entered by pressing the 'Up' key (front
panel, 4). Using the 'Up' and 'Down' keys (front panel, 4 and 2) you can scroll through several information
screens. After the last information screen the default screen will appear.
The screens display the following information:
INPUT LINE
226V
2.45kW
50Hz
OUTPUT
230V
LOAD 50%
50.0Hz
BATTERY
23°C
271V
1.9A
AUTONOMY TIME
LEFT 10:30
OPERATING TIME
0YEAR
29DAYS
OPM_LPE_11X_3K0_10K_1GB_V041
LP 5-11
LOAD 37%
Mains voltage and utility frequency, and the power delivered by the mains.
Output voltages and output frequency, and the power delivered by the UPS
(as % of the nominal UPS rating).
The temperature near the batteries, the battery voltage and the battery
current (charging: + value, discharging: - value).
The remaining battery runtime (or autonomy) during a mains failure.
The total operating time of the UPS.