1.4

Storage

• Store the UPS with its batteries fully charged in a dry location, storage temperature must be within -20
and +45°C.
• If the unit is stored for an extended period of time, the batteries must be recharged periodically.
Connect the unit to the mains and switch it on:
- if the storage temperature is within -20 and +30°C, recharge the batteries every 3 months, for 24
hours,
- if the storage temperature is within -20 and +45°C, recharge the batteries every month, for 24 hours.
1.5

Batteries

• NOTE: All maintenance and service work, including battery replacement, should be performed by
qualified service personnel.
• When replacing the batteries, use only the same type and size battery.
• Never short circuit batteries. When working with batteries, remove watches, rings or other metal
objects, and use only insulated tools.
• Avoid charging in a sealed container.
• Never dispose of batteries in a fire: they may explode.
• Do not open or mutilate batteries: their contents may be extremely toxic. If exposed to electrolyte, wash
immediately with plenty of water.
• Proper disposal or recycling of the batteries is required. Refer to your local codes for disposal
requirements.