GE Digital Energy LP 11 Operating Manual page 24

Uninterruptible power supply 3-5-6-8-10 kva
Table of Contents

Advertisement

CALIBRATE BAT
PRESS DOWN+ENTER
PF1
THYRISTOR 1
BATT.THYRISTOR 0
VSS
THYRISTOR 0
PF1. CONVERTER 1
BAT CHARGER
2
INVERTER
1
LAST TEST TIME
0:00:00
FORCE BYPASS
press DOWN+ENTER
AUTOMATIC BYPASS
ENABLED
BATTERY
7Ah
BAT. CHARGE
86%
PLL LOCK SPEED
NORMAL
IEMMODE DISABLED
ENTER/RESET CHNG
AUTO RESTART
ON
ENTER/RESET CHNG
OPM_LPE_11X_3K0_10K_1GB_V041
Start of the manual Deep Battery Calibration Test.
See for more information section 5.4.3 'Deep battery calibration test'
Service information on internal UPS components
Service information on internal UPS components
Service information on internal UPS components
Batt.Charger: 0 = off, 1 = float charging; 2 = boost charging
Duration of latest test performed, hh/mm/ss
The UPS transfers the load to bypass when the keys 'Down' (2) and
'Enter/Reset' (3) on the front panel are pressed simultaneously for approx. 2
seconds. If the bypass supply is not within limits, the lower line will show the
text 'UNAVAILABLE'.
Service set-up information whether the bypass is enabled (default) or disabled.
If disabled: UPS will NOT go to bypass. For disabling the bypass refer to the
set-up menu (5.3.4).
Service set-up information about the total battery capacity and the actual
battery charge condition. For changing the programmed battery capacity refer
to the set-up menu (5.3.4).
Service set-up information about frequency tracking speed for the inverter to
follow the bypass frequency, LOW (1Hz/sec.) is the normal value and default.
HIGH (5Hz/sec.) may be suitable if the UPS is connected to a generator with
fast frequency changes and the UPS must be synchronized to prevent alarms.
For changing the lock speed refer to the set-up menu (5.3.4).
Service set-up information about the ECO-mode. By pressing 'Enter/Reset'
the ECO-mode can be enabled or disabled, depending on the actual status.
In this way the load will be supplied by way of the electronic bypass. If the
ECO-mode is disabled the load will be supplied by the inverter. See also
5.5.5.
Service set-up information about the auto-restart function. This function can
be switched on or off by pressing 'Enter/Reset', depending on the actual
status. See also 4.5.5.1 step 6.
23
GE DE LP 11 UPS: User manual 4.1 (GB)