Analog Output Signal Ranges
-10 to 10 V
The hexadecimal values F448 to 0BB8 (-3000 to 3000) correspond to an analog voltage range of
-10 to 10 V.
The entire output range is -11 to 11V.
Specify the DA conversion data as the two's complement if it is a negative value.
F31C
8000
(−3300)
0 to 10 V
The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog voltage range of 0 to 10 V.
The entire output range is -0.5 to 10.5 V.
Specify the DA conversion data as the two's complement if it is a negative value.
8000
1 to 5 V
The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog voltage range of 1 to 5 V.
The entire output range is 0.8 to 5.2 V.
8000
CP1E CPU Unit Hardware User's Manual(W479)
9 Using Expansion Units and Expansion I/O Units
11 V
10 V
F448
(−3000)
0000 (0)
0 V
0BB8
(3000)
−10 V
−11 V
10.5 V
10 V
FED4
(−300)
0000 (0)
0 V
1770
(6000)
−0.5 V
5.2 V
5 V
1 V
0.8 V
FED4
1770
0 V
(−300)
(6000)
Conversion Data
0CE4
7FFF
Hexadecimal (Decimal)
(3300)
Conversion Data
189C
7FFF
Hexadecimal (Decimal)
(6300)
Conversion Data
7FFF
189C
Hexadecimal (Decimal)
(6300)
9