Cpu Units With 30 Or 40 I/O Points - Omron CP1E Series User Manual

Cp1e cpu unit hardware
Table of Contents

Advertisement

3 Part Names and Functions
3-1-2

CPU Units with 30 or 40 I/O Points

Part Names and Functions
E-type CPU Unit
CP1E-E30/40DR-A
Power supply
input terminals
Input terminal
block
Input
indicators
Peripheral
USB port
Analog
adjusters
Operation
indicators
External power
supply
Number
Input terminal block
Input indicators (green)
Peripheral USB port
Analog adjusters
Operation indicators
Power supply input terminal Power of 100 to 240 VAC can be supplied.
Input terminals
Ground terminal
Expansion I/O Unit connec-
tor
Output indicators (green)
Output terminal block
Output terminals
External power supply ter-
minals
Battery cover for N-type
CPU Units
3-6
Input terminals
Ground
terminal
Expansion
I/O Unit
connector
Output
indicators
Output
terminal
block
Output terminals
Name
This is the terminal block for inputs such as the power supply input and
24-VDC inputs.
Input status is displayed. An indicator will be ON when the input is ON.
Used to connect to a personal computer for programming and monitor-
ing by the CX-Programmer for CP1E.
By turning an analog adjuster, it is possible to adjust the value of A642
or A643 within a range of 0 to 255.
Refer to Section 17 Built-in Functions in the CP1E CPU Unit Soft-
ware User's Manual (Cat. No. W480).
The CPU Unit's operating status can be confirmed with this indicator.
Refer to CPU Unit Status Indicators (Page 3-7).
Input devices such as switches and sensors can be connected.
Protective ground (
less.
Functional ground (
electrical shock is a problem, connect to the protective ground terminal
and ground both with a ground of 100Ω or less.
CP-series Expansion I/O Units or Expansion Units such as Analogue
I/O Units, and Temperature Sensors can be connected.
Refer to 5-2-4 Connecting Expansion I/O Units and Expansion
Units.
Output status is displayed. An indicator will be ON when the output is
ON.
This is the terminal block for outputs such as relay outputs, transistor
outputs, and the external power supply output.
Loads such as lamps, contactors, and solenoid valves can be con-
nected.
The external supply terminals output up to 300 mA max at 24 VDC.
They can be used as a service power supply for input devices.
A Battery can be installed by opening the cover. (Battery is optional).
N-type CPU Unit
CP1E-N30/40D -
Built-in RS-232C communications
status indicator
Battery
cover
Built-in RS-232C
port
Function
): To prevent electric shock, ground to 100 Ω or