3.2.2 System Installation Illustration

The installation modes of the unit are shown in Figure 3-2 and Figure 3-3.
Note
If the condenser is installed higher than the compressor (see Figure 3-2), a back bend should be fitted to the discharge
line and liquid line of the condenser, so as to prevent the liquid refrigerant from flowing back when the condenser stops.
The top end of the back bend must be installed higher than the highest copper pipe of the condenser.

3.3 Mechanical Parameters

3.3.1 Dimensions and weight of indoor unit

The dimensions and weight of the indoor unit are shown in Figure 3-4, Figure 3-5 and Table 3-1.
Outdoor unit
Invert bend (higher than the top copper pipe of condenser)
Liquid pipe (avoid direct sun shine)
Oil trap
gas pipe slope
Sealed
Copper pipe bracket
Figure 3-2 Condenser installed higher than compressor
Figure 3-3 Condenser installed lower than compressor
Liebert. PEX+Series Precision Air Conditioner
Chapter 3 Mechanical Installation
Indoor unit
Movable floor
Thermal isolation
Floor
layer under floor
User Manual
Water inlet pipe of humidifier
Drain pipe for condensed water
9