Figure 68 Options Setup screen, page 2 of 2

OPTIONS SETUP (page 2 of 2)
S412
S413
S414
S415
S416
S417
S418
S419
S420
S421
S422
Valve Start Open—Sets position of the valve when the unit starts.
Valve Start TD—Sets a time interval for the unit to complete startup and enter into normal
operation.
3P Actuator Runtime—If Valve Control is selected for "Time" then this parameter sets the travel
time of the valve to determine the full open and closed position of the valve. This parameter is set at
the factory, based on the valve manufacturer's specifications.
3P Actuator Direction—Sets if the valve is a "Direct" or "Reverse" acting valve.
Unit Off Valve % Open—Sets the valve position when the unit is Off.

Figure 69 Module Setup screen, page 1 of 20

MODULE SETUP (page 1 of 20)
S901
S902
S903
S904
S905
S906
S907
S908
S909
S910
S911
S912
S913
PASSWORD (Actual Level 0)
Valve Start Open
Valve Start TD
3P Actuator Runtime
3P Actuator Direction
Unit Off Valve % Open
for next/previous unit
then
to change parameter
PASSWORD (Actual Level 0)
NODE ID 81
CONDENSATION DETECTED
LOCAL MODULE SHUTDOWN
SENSOR FAILURE
FAN FAILURE
FAN CONTROL MODE
DISABLE LOCAL BUTTON
FLASH LED AT MODULE
SET MODULE LABEL
SUPPLY AIR TEMP LIMITS
RETURN AIR TEMP LIMITS
FIRMWARE VERSION
Liebert iCOM Control—Firmware Version XP1.00.010.STD
to select parameter
to confirm
DELAY
EN-DIS
15
ENABLE
15
ENABLE
30
ENABLE
30
ENABLE
OFF
NO
NO
A Z 81
High 80
Low 50 °F
High 120 Low 60 °F
XXX.XX.XXX
62
UNIT 01
????
30%
90sec
70sec
Direct
30%
UNIT 01
????
TYPE
ALM
ALM
ALM