Calculating Refrigerant Charge-Example; Table 9 R-134A Refrigerant Charge For Flex Pipe Connector Lines To And From Any Model Liebert Xdo/Liebert Xdh/Liebert Xdv/Liebert Xdcf/Liebert Xdr; Table 10 Calculating Refrigerant Charge-Example; Table 11 Worksheet To Calculate Refrigerant Charge - Emerson Liebert XDP User Manual

Refrigerant distribution unit with liebert icom control
Table of Contents

Advertisement

Table 9
R-134a refrigerant charge for Flex Pipe connector lines to and from any model
Liebert XDO/Liebert XDH/Liebert XDV/Liebert XDCF/Liebert XDR
Refrigerant Charge
lb. (kg)
Supply Line Diameter 1/2"
0.3 lb. (0.14)
0.5 lb. (0.23)
0.7 lb. (0.32)
0.8 lb. (0.36)
Return Line Diameter 5/8"
0.01 lb. (0.01)
0.02 lb. (0.01)
0.03 lb. (0.01)
0.03 lb. (0.01)
Return Line Diameter 1"
0.13 lb. (0.06)
0.2 lb. (0.09)
0.27 lb. (0.12)
0.33 lb. (0.15)
3.6.1
Calculating Refrigerant Charge—Example
Using Tables 6, 7, 8 and 9, calculate the refrigerant charge of the individual sections of your Liebert
XD system. Add the calculated charge amounts to determine the amount of R-134a refrigerant
required for one system combining a Liebert XDP with Liebert XD cooling modules (Liebert XDCF,
Liebert XDH, Liebert XDO and Liebert XDV). The example below combines one Liebert XDP with 20
Liebert XDV8 cooling modules.
Table 10
Calculating refrigerant charge—example
Components
Liebert XDP
Liebert XDV8 Cooling Modules
Supply Main, 1-1/8"
Return Main, 2-1/8"
Liebert XDV 1/2" supply Liebert XD Flex Pipes
Liebert XDV 5/8" return Liebert XD Flex Pipes
Table 11
Worksheet to calculate refrigerant charge
Components
Metal Flex Pipe Connector Length
4 ft. Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF/Liebert XDR supply
6 ft. Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF/Liebert XDR supply
8 ft. Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF/Liebert XDR supply
10 ft. Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply/Liebert XDR
4 ft. Flex Pipe existing Liebert XDV systems
6 ft. Flex Pipe existing Liebert XDV systems
8 ft. Flex Pipe existing Liebert XDV systems
10 ft. Flex Pipe existing Liebert XDV systems
4 ft. Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF/Liebert XDR supply
6 ft. Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF/Liebert XDR supply
8 ft. Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF/Liebert XDR supply
10 ft. Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF/Liebert XDR supply
Number of Units
or Piping Length, feet
1
20
100
100
20
20
Number of Units
or Piping Length
24
Piping
Pounds Per
Component
Total, lb.
157
157
2.32
46.4
0.45
0.28
0.8
0.03
Total
293
Pounds Per
Component
Total
Total
45
28
16
0.6