Warning Signal If Battery System Not Connected; Warning Signal For Phase Loss Or Phase Sequence Error - AEG Protect 1. M Operating Instructions Manual

Table of Contents

Advertisement

Warning Signal if Battery System Not
11.4
Connected,
Operating
LED indications
status /
Operating
problems
Bypass
mode
Normal
mode
Warning Signal for Phase Loss or Phase
11.5
Sequence Error
Operating
LED indications
status /
Operating
problems
Phase loss;
Phase
sequence
error; bypass
Mains failure
normal mode
Note:
= LED lights up
= LED flashes
e.g. battery fuse failure
Warning signal
1 acoustic signal
every 4 s
1 acoustic signal
every 4 s
Warning signal
1 acoustic signal
every 2 s
1 acoustic signal
every 4 s
46
LC displays
Notes
"UPS is not
Check battery
connected to
system; poss.
the battery"
fuse fault?
"UPS is not
Check battery
connected to
system;
the battery"
fuse fault?
LC displays
Notes
"utility failure
No output
and sequence
voltage; check
error"
UPS connection
"utility failure"
Check UPS
alarm code
input cabling
02 03 09
poss.