AEG Protect 1. M Operating Instructions Manual page 11

Table of Contents

Advertisement

Frequency
Frequency tolerance range
Current consumption at full load (max.)
PROTECT 1.M (system)
PROTECT 1.040 (module)
System disturbance factor
UPS output
Nominal voltage output
Nominal frequency
Type of voltage
Crest factor
Overload behaviour
with mains supply
Overload behaviour with
battery operation
Short-circuit behaviour
176 VAC – 264 VAC ±3%
(Bypass)
50 Hz / 60 Hz
(Automatic detection)
±4 Hz
44 A (3ph~) or 132 A (1ph~) / 155
A (Bypass)
7.3 A (3ph~) or 22 A (1ph~)
λ ≥ 0.98
220 / 230 / 240 Vac ±2%
(configuration via "CompuWatch"
software)
50 Hz / 60 Hz ±0.2 Hz (dependent
on mains frequency)
Sine, distortion
< 3% THD (linear load)
< 6% THD (non-linear load)
3:1
Up to 105% continuous;
> 105% – < 130% for 30s
130% for 2 s
Following this, automatic,
uninterrupted switchover to
integrated bypass (SBS).
Switch-off after 1 min. if overload
continues to be present (switch
back if overload decreases = load
< 90%)
Up to 105% continuous;
> 105% – < 130% for 30s
130% for 2 s
3 x I
for 100 ms
N
11