AEG Protect 1. M Operating Instructions Manual page 13

Table of Contents

Advertisement

Site altitude
Housing colour
Weight:
PROTECT 1.M (chassis)
PROTECT 1.040 (module)
Dimensions W x H x D:
PROTECT 1.M (chassis)
PROTECT 1.040 (module)
Directives
The PROTECT 1.M meets the product standard EN 50091.
The CE mark on the unit confirms compliance with the EC
outline directives for 73/23 EEC – Low voltage and for 89/336
EEC – Electromagnetic compatibility if the installation
instructions described in the operating instructions are
observed.
For 73/23 EEC low-voltage directive
reference number
For 89/336 EMC directive
reference number
Warning:
i
This is a class A - device. This product can
generate radio interference in the domestic
environment. In this case, the user can be
required to employ additional interference
suppression measures.
Up to 1000 m at nominal output
Use more than 1000 m above sea
level results in the following
reduction in output power:
Height (m) 1000
Power
100%
Blackline
75 kg
15 kg per module
442 mm x 965 mm x 700 mm
405 mm x 87 mm x 530 mm
EN 62040-1-1 : 2003
EN 50091-2 :
EN 61000-3-2 : 1995
EN 61000-3-3 : 1995
13
1500
2000
2500
95%
90%
85%
1995
3000
80%