Alarm Code Output; Resetting The Inverter - Mitsubishi Electric FR-A500L Series Instruction Manual

Large capacity inverter fr-a560l-375k~900k-na
Table of Contents

Advertisement

5.1.3 Alarm code output

By setting Pr. 76 "alarm code output selection", an alarm definition can be output as a 4-bit digital signal. This
signal is output from the open collector output terminals equipped as standard on the inverter.
Correlations between alarm definitions and alarm codes are as follows.
Operation Panel
Display
•i
•j
FR-DU04
E.OC1
E.OC2
E.OC3
E.OV1
E.OV2
E.OV3
E.THM
E.THT
E.IPF
E.UVT
E.FIN
E. 15
E. GF
E.OHT
E.OLT
E.OPT
E.OP1 to E.OP3
E. PE
E.PUE
E.RET
E.LF
E.CPU
E.14

5.1.4 Resetting the inverter

The inverter can be reset by performing any of the following operations. Note that the electronic overcurrent
protection's internal heat calculation value and the number of retries are cleared (erased) by resetting the inverter.
Operation 1: Using the operation panel (FR-DU04), press the [RESET] key to reset the inverter.
Operation 2: Switch power off once, then switch it on again.
Operation 3: Switch on the reset signal (RES).
Output Terminal Signal On-Off
SU
IPF
OL
0
0
0
0
0
1
0
0
1
0
1
0
0
1
0
0
1
1
0
1
1
1
0
0
1
0
0
1
0
1
1
0
1
1
1
0
1
1
0
1
1
1
1
1
1
1
1
1
(Note) 0: Output transistor OFF, 1: Output transistor ON (common terminal SE)
The alarm output assumes that Pr. 195 setting is "99" (factory setting).
PROTECTIVE FUNCTIONS
Alarm Code
FU
1
1
0
2
1
3
0
4
1
5
0
6
1
7
0
8
1
9
0
A
1
B
0
C
1
D
0
E
0
E
1
F
29
Alarm Output (across B-C)
Provided (Open)
Provided (Open)
Provided (Open)
Provided (Open)
Provided (Open)
Provided (Open)
Provided (Open)
Provided (Open)
Provided (Open)
Not provided (Provided when OLT
is displayed) (Open)
Provided (Open)
Provided (Open)
Provided (Open)
Provided (Open)
Provided (Open)
Provided (Open)
Provided (Open)
Provided (Open)