Mitsubishi Electric FR-A500L Series Instruction Manual page 48

Large capacity inverter fr-a560l-375k~900k-na
Table of Contents

Advertisement

Checking the inverter and converter modules
<Preparation>
(1) Disconnect the external power supply cables (R, S, T) <L
(2) Prepare a tester. (Use 100 range.)
<Checking method>
Change the polarity of the tester alternately at the inverter terminals R, S, T, U, V, W, P and N <L
W, + and ->, and check for continuity.
Note: 1. Before measurement, check that the smoothing capacitor is discharged.
2. At the time of continuity, the measured value is several to several ten's-of ohms depending on the
module type, circuit tester type, etc. If all measured values are almost the same, the modules are
without fault.
<Module device numbers and terminals to be checked>
Tester Polarity
R<L
>
P<+>
1
D1
P<+>
R<L
1
S<L
>
P<+>
2
D2
P<+>
S<L
2
T<L
>
P<+>
3
D3
P<+>
T<L
>
3
U
P<+>
TR1
P<+>
U
V
P<+>
TR2
P<+>
V
W
P<+>
TR5
P<+>
W
Converter module
D1
D2
D3
R
<L
>
1
S
<L
>
2
T
<L
>
3
D4
D5
D6
Measured
Value
Discontinuity
D4
>
Continuity
Discontinuity
D5
>
Continuity
Discontinuity
D6
Continuity
Discontinuity
TR4
Continuity
Discontinuity
TR6
Continuity
Discontinuity
TR2
Continuity
P<+>
Inverter module
TR1
TR3
C
TR4
TR6
N
<->
, L
, L
1
2
Tester Polarity
Measured
Value
R<L
>
N<->
Continuity
1
N<->
R<L
>
Discontinuity
1
S<L
>
N<->
Continuity
2
N<->
S<L
>
Discontinuity
2
T<L
>
N<->
Continuity
3
N<->
T<L
>
Discontinuity
3
U
N<->
Continuity
N<->
U
Discontinuity
V
N<->
Continuity
N<->
V
Discontinuity
W
N<->
Continuity
N<->
W
Discontinuity
TR5
U
V
W
TR2
37
PROTECTIVE FUNCTIONS
> and motor cables (U, V, W).
3
, L
, L
U, V,
1
2
3,

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a560l-375kFr-a560l-450kFr-a560l-900kFr-a560l-530k