2.2.3 Wiring of the control circuit

( 1 ) Wiring instructions
1) Terminals SD, SE and 5 are common to the I/O signals and isolated from each other. These common terminals
must not be connected to each other or earthed.
2) Use shielded or twisted cables for connection to the control circuit terminals and run them away from the main
and power circuits (including the 200V relay sequence circuit).
3) The frequency input signals to the control circuit are micro currents. When contacts are required, use two or
more parallel micro signal contacts or a twin contact to prevent a contact fault.
4) It is recommended to use the cables of 0.75mm
If the cable gauge used is 1.25mm
or the cables are run improperly, resulting in an operation panel or parameter unit contact fault.
( 2 ) Terminal block layout
l NA version•iOR Version•j
In the control circuit of the inverter, the terminals are arranged as shown below:
Terminal screw size: M3.5
l EC version
Terminal screw size : M3
A
B
C
SE
RUN
SU
<Wiring procedure>
1)
For the wiring of the control circuit, strip the sheaths of the cables and use them as they are.
Strip the sheath to the following dimension. If too much is stripped this may cause a short circuit with
the neighboring cable. If too little stripped this may cause cable disconnection.
2) Loosen the terminal screw and insert the cable into the terminal.
3) Tighten the screw to the specified torque.
Undertigthening can cause cable disconnection or malfunction. Overtightening can cause a short circuit or
malfunction due to the screw or unit damaged.
Tightening torque : 5 to 6 kgf¥cm
Note : Wire the stripped cable by twisting it to prevent it from becoming loose. (Do not plate the cable with
solder.)
Note : 1. Use a NFB (No fuse breakers) or fuse on the inverter input (primary) side.
2. Make sure that the control circuit terminal wiring does not touch power circuit terminals (or
screws) or conducting power circuit.
2
or more, the front cover may be lifted when there are many cables running
A
B
C
PC
RL
RM
RH
SE
RUN
SU
IPF
SD
AM
10E
10
2
LPF
OL
FU
STOP
6mm
1mm
INSTALLATION AND WIRING
2
gauge for connection to the control circuit terminals.
AM
10 E
10
2
5
RT
AU
STOP MRS
RES
SD
OL
FU
SD
STF
STR
5
4
1
RL
MRS
RES
PC
STF
STR
12
4
1
FM
JOG
CS
RM
RH
RT
AU
JOG
CS
FM
SD

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a560l-375kFr-a560l-450kFr-a560l-900kFr-a560l-530k

Table of Contents