Plug the output module into the special UPS output receptacle, located on the rear of the UPS.
b.
Item
1
2
3
4
5
6

Charging the UPS batteries

With the UPS in Standby mode, allow the batteries to charge before putting the UPS into service.
IMPORTANT:
devices. The batteries charge to:

Powering up the standalone UPS

NOTE:
overload alarm.
Switch the UPS input circuit breaker to the On position.
1.
Wait for the UPS front panel display to illuminate.
2.
The Alarm LED flashes.
Check the UPS front panel display for active alarms or notices (other than "Batteries Disconnected").
3.
Resolve any active alarms before continuing. For more information, see "Troubleshooting (on page
94)" .
Switch the UPS battery circuit breaker to the On position.
4.
Description
Rack corner post
Mounting locations
Mounting top bracket
Output cord
Mounting bottom bracket
Input cord
Charge the batteries for at least 48 hours before supplying backup power to
80 percent of their capacity within 5 hours
100 percent of their capacity within 48 hours
Be sure that the total equipment ratings do not exceed the UPS capacity to prevent an
UPS installation 25